59/130
Siemens Building Technologies
Basic Documentation RVD230
CE1P2383en
HVAC Products
14 Function block Valve actuator heat converter / primary controller
27.05.2004
Voltage
Temperature when operat-
ing line 89 = 80 °C
Temperature when operat-
ing line 89 = 130 °C
DC 0 V
0 °C
0 °C
DC 5 V
40 °C
65 °C
DC 10 V
80 °C
130 °C
The controller considers signals below DC 0.4 V as no heat demand signals.