113/130
Siemens Building Technologies
Basic Documentation RVD230
CE1P2383en
HVAC Products
33 Engineering
27.05.2004
33 Engineering
33.1 Connection terminals
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
2383
Z
03
A6 MD B9 B1 M B3 B7
B71
/U1
M
M
H5
N
L
F1 Y1
Y2
F3 Q1
F4 Y5 Y6 F7
N
DB MB
P1
B31
B72
B32
B12
CM
+
CM
-
-
Q3
Q2 -
-
F6
Y7
Q4
Y8
K6
A6
PPS (point-to-point interface), connection of room unit / room temperature sensor QAW70, QAW50 /
QAA10
B1
Flow sensor
B12
Additional heating circuit or d.h.w. flow sensor
B3
D.h.w. flow sensor
B31
Storage tank sensor
B32
Storage tank or return sensor
B7
Primary return sensor
B71 / U1 Return sensor / analog input DC 0…10 V
B72 Return
sensor
B9 Outside
sensor
CM–
Digital M-bus connection facility (bipolar)
CM+
Digital M-bus connection facility (bipolar)
DB
LPB connection facility
H5
Digital input (heat meter pulses, alarms, flow switch, external heat demand)
M
Ground for sensors (analog)
MB LPB
ground
MD
Ground for PPS (digital)
P1
PWM output for speed-controlled pumps
L
Live AC 230 V
N
Neutral AC 230 V
F1
Input for Y1 and Y2
Y1
Control output for valve on the primary side OPEN
Y2
Control output for valve on the primary side CLOSED
F3
Input for Q1 and Q3
Q1
Control output for heating circuit / system pump ON
Q3
Control output for d.h.w. intermediate circuit pump or diverting valve ON
F4
Input for Y5 and Y6
Y5
Control output for d.h.w. valve OPEN
Y6
Control output for d.h.w. valve CLOSED
F7 Input
for
Q2
Q2
Heating circuit / storage tank charging pump ON
F6
Input for Y7/Q4 and Y8/K6
Y7
Control output for valve OPEN
Y8
Control output for valve CLOSED
Q4
Control output for d.h.w. intermediate circuit / storage tank charging pump
K6
Control output for circulating pump ON
The base contains 2 auxiliary terminals N and
Low-voltage side
Mains voltage side