Technical Specifications
5
This section provides important technical specifications related to the device.
5.1
Power Supply Specifications
Note
When determining cable lengths, make sure the nominal input voltage for the power
supply is provided at the power source.
Hazardous Environments
Input Voltage
Power
Supply Type
Minimum
Maximum
Nominal
Internal
Fuse Rating
Isolation
Maximum
Power
Consumption
LO
11.1 VDC
55 VDC
12 VDC, 24
VDC, 48 VDC
5 A
1.5 kVDC
13.4 W
100 VDC
270 VDC
125 VDC,
250 VDC
3.15 A
5 kVDC
15.3 W
HI
100 VAC
240 VAC
110 VAC,
220 VAC
3.15 A
5 kVDC
15.5 W
Current consumption may vary based on configuration.
Non-Hazardous Environments
Input Voltage
Power
Supply Type
Minimum
Maximum
Nominal
Internal
Fuse Rating
Isolation
Maximum
Power
Consumption
LO
10 VDC
60 VDC
12 VDC, 24
VDC, 48 VDC
5 A
1.5 kVDC
13.4 W
88 VDC
300 VDC
125 VDC,
250 VDC
3.15 A
5 kVDC
15.3 W
HI
85 VAC
264 VAC
110 VAC,
220 VAC
3.15 A
5 kVDC
15.5 W
Current consumption may vary based on configuration.
RUGGEDCOM RSG908C
Installation Manual, 04/2022, C79000-G8976-1404-11
25