Certification
6.2 EMC and Environmental Type Tests
Description
Test Levels
DC Power Ports
5 kV
AC Power Ports
5 kV
Signal Ports
2 kV (Failsafe Relay)
DC Power Ports
1.5 kV
Dielectric Strength
AC Power Ports
2 kV
Environmental Type Tests
Test
Description
Test Levels
Severity Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40
°F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185
°F), 16 Hours
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (Non-
Condensing),
55 °C (131
°F), 6 Cycles
IEC 60255-21-1
Vibration
2 g @ 10 to 150 Hz
Class 2
IEC 60255-21-2
Shock
30 g @ 11 ms
Class 2
36
RUGGEDCOM RS900
Installation Manual, 12/2020, C79000-G8976-1024-12