Certification
6.2 EMC and Environmental Type Tests
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS900 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure
Contact
± 8 kV
4
IEC
61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC
61000-4-3
Radiated RFI
Enclosure
Ports
20 V/m
Signal Ports
± 4 kV @ 2.5 kHz
x
DC Power
Ports
± 4 kV
4
AC Power
Ports
± 4 kV
4
IEC
61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 4 kV
4
Signal Ports
± 4 kV Line-to-Ground
± 2 kV
4
DC Power
Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC
61000-4-5
Surge
AC Power
Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal Ports
10 V
3
DC Power
Ports
10 V
3
AC Power
Ports
10 V
3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V
3
IEC
61000-4-8
Magnetic Field
Enclosure
Ports
40 A/m Continuous
1000 A/m for 1 s
IEC
61000-4-11
Voltage Dips and Interrupts
AC Power
Ports
100% for 5 Periods
100% for 50 Periods
Signal Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
DC Power
Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
AC Power
Ports
2.5 kV Common
Mode @ 1 MHz
3
34
RUGGEDCOM RS900
Installation Manual, 12/2020, C79000-G8976-1024-12