RUGGEDCOM M2200
Installation Guide
Chapter 1
Introduction
Supported Fiber Optic Cables
5
Cabling Category
1000Base-
TX Compliant
Required Action
6
Yes
No action required.
> 6
Yes
Connector and wiring standards to be determined.
Follow these recommendations for copper data cabling in high electrical noise environments:
• Data cable lengths should be as short as possible, preferably 3 m (10 ft) in length. Copper data cables should
not be used for inter-building communications.
• Power and data cables should not be run in parallel for long distances, and should be installed in separate
conduits. Power and data cables should intersect at 90° angles when necessary to reduce inductive coupling.
• Shielded/screened cabling can be used when required. Care should be taken to avoid the creation of ground
loops with shielded cabling.
Section 1.5.3
Supported Fiber Optic Cables
The following fiber optic cable types are supported under the stated conditions.
Distance (m)
Cable Type
Wavelength (nm)
Modal Bandwidth
(MHz·km)
100Base-FX
1000Base-SX
10GBase-SR
850
200
—
275
33
OM1 (62.5/125)
1300
500
2000
—
—
850
500
—
550
82
OM2 (50/125)
1300
500
2000
—
—
850
1500
—
550
300
OM3 (50/125)
a
1300
500
2000
—
—
850
3500
—
550
400
OM4 (50/125)
a
1300
500
2000
—
—
a
Laser optimized.
Summary of Contents for RUGGEDCOM M2200
Page 4: ...RUGGEDCOM M2200 Installation Guide iv ...
Page 10: ...Preface RUGGEDCOM M2200 Installation Guide x Customer Support ...
Page 16: ...Chapter 1 Introduction RUGGEDCOM M2200 Installation Guide 6 Supported Fiber Optic Cables ...
Page 28: ...Chapter 2 Installing Device RUGGEDCOM M2200 Installation Guide 18 Wiring Examples ...
Page 42: ...Chapter 5 Technical Specifications RUGGEDCOM M2200 Installation Guide 32 Dimension Drawings ...