5 / 12 

Siemens 

Semi-flush-mount Room Thermostats with LCD 

CB1N3064en 

Building Technologies 

 

24.08.2010 

4. 

By pressing b and 

 simultaneously, the current value of the selected 

parameter appears, which can be changed by repeatedly pressing b 
or 

5. 

By pressing b and 

 simultaneously again, the next parameter will be 

display. Or, 5 seconds after the last press of the button, the last parameter will 
be displayed again. 

6. 

If you wish to display and change additional parameters, repeat steps 3 
through 5. 

7. 

Otherwise, press + or 

 until 

End

 is displayed, and then press + and 

 simul-

taneously to save the change and exit parameter entry mode. 

The factory setting of the control parameters can be reloaded as follows: 

1. 

Set the controller to Protection mode 

2. 

Press b and 

 simultaneously for 3 seconds. Release them and, within 

2 seconds, press Fan mode button twice. 

3. 

Then, the display will show 

888

 during the reloading process. 

Para-

meter 

Meaning 

Setting range 

Factory 

setting 

P03 

Setpoint of heating in Protection 
Mode 

   

(Wheat

Stb

OFF, 5 

°

C

Wcool

Stb

 

°

P04 

Setpoint of cooling in Protection 
Mode 

   

(Wcool

Stb

OFF, Wheat

Stb

40 

°

OFF 

P05 

Minimum setpoint limitation in 
Comfort Mode  (Wmin

Comf

°

C

Wmax

Comf

 

°

P06 

Maximum setpoint limitation in 
Comfort Mode  (Wmax

Comf

Wmin

Comf

40 

°

35 

°

P07  Sensor calibration 

-3

3 K 

0 K 

P08 

Switching differential heating mode 
(SDH) 

0.5

4 K 

1 K 

P09 

Switching differential cooling mode 
(SDC) 

0.5

4 K 

1 K 

P14  Dwelling time of auto fan speeds 

1

5 mins 

2 min 

P17  Selection of 

°

C or 

°

°

C or 

°

°

P18  Display of temperature or setpoint 

OFF: Setpoint 
ON: Room (or return air)
 

temperature 

ON 

P21 

Fan control in Normal operation 
(Comfort mode) 

OFF in dead zone  
ON in dead zone 

ON 

P22  Heat/Cool mode 

0: Heating only 
1: Cooling only 
3: Manual H/C changover 

3: Manual 

P26 

Button lock 
(Pressing 7 seconds on the oper-
ating mode button, the buttons will 
be locked or unlocked respec-
tively) 

0: Disabled 
1: Auto lock 
2: Manual lock 

0: Disabled 

Parameter reset 

Control parameter list 

Summary of Contents for RDF510.2

Page 1: ...l Automatic or manual Manual heating cooling changeover or continuous Cooling only or Heating only Operating modes Comfort Protection Adjustable commissioning and control parameters Optional display of room temperature or setpoint Minimum and maximum setpoint limitation Display temperature in increments of 0 5 C or 1 F Operating voltage AC 230 V Mounting on recessed rectangular conduit box with fi...

Page 2: ...mode adjust able via parameters P08 and P09 The display can show current room temperature or the setpoint adjusted by user This can be selected via parameter P18 factory setting is the current room tem perature The heating and cooling symbols on the display show the status of the fan coil This means that the symbols are also shown while the controller operates in the dead zone If required room tem...

Page 3: ...output Y11 was energized for more than 1 minute the Minimum output on time is a fix value Control output Y12 delivers a control command which is inverted to the control command at output Y11 and which can be used for open valves normally When pressing the Heat Cool mode selector the controller will change from heat ing to cooling or vice versa If the controller is set to Cooling only or Heating on...

Page 4: ...fan motor starts to overcome inertia and friction Error handling When the room temperature is out of the measuring range which means above 49 C or below 0 C the display shows the limiting temperature in flashing figures 0 C or 49 C If the current setpoint is not OFF see parameters P03 and the controller is in heating mode when the temperature is below 0 C output Y11 will be energized In all other ...

Page 5: ...ill show 888 during the reloading process Para meter Meaning Setting range Factory setting P03 Setpoint of heating in Protection Mode WheatStb OFF 5 C WcoolStb 8 C P04 Setpoint of cooling in Protection Mode WcoolStb OFF WheatStb 40 C OFF P05 Minimum setpoint limitation in Comfort Mode WminComf 5 C WmaxComf 5 C P06 Maximum setpoint limitation in Comfort Mode WmaxComf WminComf 40 C 35 C P07 Sensor c...

Page 6: ...21 N4863 N4863AP Thermal actuator for radiator valves small valves and zone valves STA21 N4877 Thermal actuator for terminal unit valves STP21 N4878 Electric actuator for zone valves SUA N4832 Conduit box for semi flush mount thermostat ARG71 S55770 T137 N3009 Only available in AP UAE SA and IN Ordering When ordering please indicate the product name product number and SSN num ber Room Thermostat R...

Page 7: ...parameters Symbol used when displaying the current room temperature Fan mode and fan speed indicator Automatic fan active Manual fan active Fan mode button changing the fan mode Auto manual changing the fan speed Low Medium High Heat Cool mode selector For the changeover between cooling mode and heating mode if P22 3 Or Operating mode button For the selection of comfort mode and protection mode Or...

Page 8: ...egments displayed indicating that the reset has been correctly made This takes about 3 seconds Then the controller is ready for commissioning by qualified HVAC staff The control parameters of the controller can be set to ensure optimum performance of the entire system please refer to Parameter Settings Depending on the application the Heat Cool mode must be set via parameter P22 Factory setting is...

Page 9: ...oling mode 20 C 8 C OFF Built in room temperature sensor Measuring range Accuracy at 25 C Temperature calibration range 0 49 C 0 5 K 3 K Resolution of settings and display Setpoints Current temperature value displayed 0 5 C 0 5 C Operation Climatic conditions Temperature Humidity to IEC 721 3 3 class 3K5 0 50 C 95 r h Transport Climatic conditions Temperature Humidity Mechanical conditions to IEC ...

Page 10: ...gree of protection of housing IP 30 as per EN 60529 Connection terminals solid wires or prepared stranded wires 2 x 0 4 1 5 mm 2 or 1 x 0 4 2 5 mm 2 Weight 0 17 kg Color of housing front white RAL 9003 Connection terminals L N Operating voltage AC 230 V Q1 Control output Fan speed 1 AC 230 V Q2 Control output Fan speed 2 AC 230 V Q3 Control output Fan speed 3 AC 230 V Y11 Control output Valve AC 2...

Page 11: ...11 12 Siemens Semi flush mount Room Thermostats with LCD CB1N3064en Building Technologies 24 08 2010 Dimensions ...

Page 12: ...12 12 Siemens Semi flush mount Room Thermostats with LCD CB1N3064en Building Technologies 24 08 2010 2010 Siemens Schweiz AG Subject to change ...