5 / 12
Siemens
Semi-flush-mount Room Thermostats with LCD
CB1N3064en
Building Technologies
24.08.2010
4.
By pressing b and
–
simultaneously, the current value of the selected
parameter appears, which can be changed by repeatedly pressing b
or
–
.
5.
By pressing b and
–
simultaneously again, the next parameter will be
display. Or, 5 seconds after the last press of the button, the last parameter will
be displayed again.
6.
If you wish to display and change additional parameters, repeat steps 3
through 5.
7.
Otherwise, press + or
–
until
“
End
”
is displayed, and then press + and
–
simul-
taneously to save the change and exit parameter entry mode.
The factory setting of the control parameters can be reloaded as follows:
1.
Set the controller to Protection mode
.
2.
Press b and
–
simultaneously for 3 seconds. Release them and, within
2 seconds, press Fan mode button twice.
3.
Then, the display will show
“
888
”
during the reloading process.
Para-
meter
Meaning
Setting range
Factory
setting
P03
Setpoint of heating in Protection
Mode
(Wheat
Stb
)
OFF, 5
°
C
…
Wcool
Stb
8
°
C
P04
Setpoint of cooling in Protection
Mode
(Wcool
Stb
)
OFF, Wheat
Stb
…
40
°
C
OFF
P05
Minimum setpoint limitation in
Comfort Mode (Wmin
Comf
)
5
°
C
…
Wmax
Comf
5
°
C
P06
Maximum setpoint limitation in
Comfort Mode (Wmax
Comf
)
Wmin
Comf
…
40
°
C
35
°
C
P07 Sensor calibration
-3
…
3 K
0 K
P08
Switching differential heating mode
(SDH)
0.5
…
4 K
1 K
P09
Switching differential cooling mode
(SDC)
0.5
…
4 K
1 K
P14 Dwelling time of auto fan speeds
1
…
5 mins
2 min
P17 Selection of
°
C or
°
F
°
C or
°
F
°
C
P18 Display of temperature or setpoint
OFF: Setpoint
ON: Room (or return air)
temperature
ON
P21
Fan control in Normal operation
(Comfort mode)
OFF in dead zone
ON in dead zone
ON
P22 Heat/Cool mode
0: Heating only
1: Cooling only
3: Manual H/C changover
3: Manual
P26
Button lock
(Pressing 7 seconds on the oper-
ating mode button, the buttons will
be locked or unlocked respec-
tively)
0: Disabled
1: Auto lock
2: Manual lock
0: Disabled
Parameter reset
Control parameter list