2 / 12 

Siemens 

Semi-flush-mount Room Thermostats with LCD 

CB1N3064en 

Building Technologies 

 

24.08.2010 

Use 

For controlling the room temperature in individual rooms and zones that are: 

  heated or cooled with 2-pipe fan coil units 

  cooled with a single compressor in DX type equipment 

The controller controls: 

  a 3-speed fan 

  either a valve actuator in a 2-pipe system, or 

  a 3-wire ball valve actuator in a 2-pipe system, or 

  a 1-stage compressor in DX type equipment 

Suitable for use in systems with: 

  continuous heating or cooling mode 

  manual heating/cooling changeover 

Functions 

  Changeover between heating and cooling mode is manually 

  Maintenance of room temperature with integrated temperature sensor 

  Selection of operating mode with the operating mode button on the controller 

  3-speed fan control (automatic or manual) 

  Output for 2-position (on/off) valve actuator, 3-wire (on/off) valve actuator or 1-

stage compressor 

  Button lock (automatic or manual) 

Controller 

The controller acquires the room temperature via its built-in sensor and maintains 
the setpoint by delivering 2-position valve control commands or compressor output 
commands. 
The switching differential is 1 K in heating mode and 1 K in cooling mode (adjust-
able via parameters P08 and P09). 

The display can show current room temperature or the setpoint adjusted by user. 
This can be selected via parameter P18 (factory setting is the current room tem-
perature). 
The heating 

 and cooling 

 symbols on the display show the status of the fan 

coil. This means that the symbols are also shown while the controller operates in 
the dead zone. 
If required, room temperature and setpoint can also be displayed in 

°

F in place of 

°

C by changing parameter P17. 

Operating modes 

The following operating modes are available: 

In Comfort mode, the controller maintains the setpoint, which can be adjusted via 
the + and 

 buttons. The fan can be set to automatic or manual fan speed: Low, 

medium or high. 
The setpoint setting range can be limited to a minimum (P05) and maximum (P06). 
This helps prevent the waste of energy, thus saving costs. 

When the controller is in Protection mode 

, the relevant setpoints of heating or 

cooling are maintained. These setpoints can be adjusted via control parameters 
P03 and P04. Factory setting of P03 is 8

 

°

C; whereas P04 is OFF, which means 

that the controller is not activated when in Protection mode. 

To avoid damage due to moisture in very warm and humid climatic zones resulting 
from lack of air circulation in normal operation (Comfort mode 

), the fan can be 

Temperature control 

Display 

Comfort Mode 

 

Tips 

Protection Mode 

 

Avoiding damage 
due to moisture 

Summary of Contents for RDF510.2

Page 1: ...l Automatic or manual Manual heating cooling changeover or continuous Cooling only or Heating only Operating modes Comfort Protection Adjustable commissioning and control parameters Optional display of room temperature or setpoint Minimum and maximum setpoint limitation Display temperature in increments of 0 5 C or 1 F Operating voltage AC 230 V Mounting on recessed rectangular conduit box with fi...

Page 2: ...mode adjust able via parameters P08 and P09 The display can show current room temperature or the setpoint adjusted by user This can be selected via parameter P18 factory setting is the current room tem perature The heating and cooling symbols on the display show the status of the fan coil This means that the symbols are also shown while the controller operates in the dead zone If required room tem...

Page 3: ...output Y11 was energized for more than 1 minute the Minimum output on time is a fix value Control output Y12 delivers a control command which is inverted to the control command at output Y11 and which can be used for open valves normally When pressing the Heat Cool mode selector the controller will change from heat ing to cooling or vice versa If the controller is set to Cooling only or Heating on...

Page 4: ...fan motor starts to overcome inertia and friction Error handling When the room temperature is out of the measuring range which means above 49 C or below 0 C the display shows the limiting temperature in flashing figures 0 C or 49 C If the current setpoint is not OFF see parameters P03 and the controller is in heating mode when the temperature is below 0 C output Y11 will be energized In all other ...

Page 5: ...ill show 888 during the reloading process Para meter Meaning Setting range Factory setting P03 Setpoint of heating in Protection Mode WheatStb OFF 5 C WcoolStb 8 C P04 Setpoint of cooling in Protection Mode WcoolStb OFF WheatStb 40 C OFF P05 Minimum setpoint limitation in Comfort Mode WminComf 5 C WmaxComf 5 C P06 Maximum setpoint limitation in Comfort Mode WmaxComf WminComf 40 C 35 C P07 Sensor c...

Page 6: ...21 N4863 N4863AP Thermal actuator for radiator valves small valves and zone valves STA21 N4877 Thermal actuator for terminal unit valves STP21 N4878 Electric actuator for zone valves SUA N4832 Conduit box for semi flush mount thermostat ARG71 S55770 T137 N3009 Only available in AP UAE SA and IN Ordering When ordering please indicate the product name product number and SSN num ber Room Thermostat R...

Page 7: ...parameters Symbol used when displaying the current room temperature Fan mode and fan speed indicator Automatic fan active Manual fan active Fan mode button changing the fan mode Auto manual changing the fan speed Low Medium High Heat Cool mode selector For the changeover between cooling mode and heating mode if P22 3 Or Operating mode button For the selection of comfort mode and protection mode Or...

Page 8: ...egments displayed indicating that the reset has been correctly made This takes about 3 seconds Then the controller is ready for commissioning by qualified HVAC staff The control parameters of the controller can be set to ensure optimum performance of the entire system please refer to Parameter Settings Depending on the application the Heat Cool mode must be set via parameter P22 Factory setting is...

Page 9: ...oling mode 20 C 8 C OFF Built in room temperature sensor Measuring range Accuracy at 25 C Temperature calibration range 0 49 C 0 5 K 3 K Resolution of settings and display Setpoints Current temperature value displayed 0 5 C 0 5 C Operation Climatic conditions Temperature Humidity to IEC 721 3 3 class 3K5 0 50 C 95 r h Transport Climatic conditions Temperature Humidity Mechanical conditions to IEC ...

Page 10: ...gree of protection of housing IP 30 as per EN 60529 Connection terminals solid wires or prepared stranded wires 2 x 0 4 1 5 mm 2 or 1 x 0 4 2 5 mm 2 Weight 0 17 kg Color of housing front white RAL 9003 Connection terminals L N Operating voltage AC 230 V Q1 Control output Fan speed 1 AC 230 V Q2 Control output Fan speed 2 AC 230 V Q3 Control output Fan speed 3 AC 230 V Y11 Control output Valve AC 2...

Page 11: ...11 12 Siemens Semi flush mount Room Thermostats with LCD CB1N3064en Building Technologies 24 08 2010 Dimensions ...

Page 12: ...12 12 Siemens Semi flush mount Room Thermostats with LCD CB1N3064en Building Technologies 24 08 2010 2010 Siemens Schweiz AG Subject to change ...

Reviews: