background image

Siemens

RDD100.1RFS

Building Technologies

Equipment combinations

Mechanical design

The room thermostat consists of

Plastic housing which accommodates the electronics, the operating
and the room temperature sensor

Mounting plate

Table stand

The housing engages in the mounting plate and
The optional table stand snap

The RCR100RF receiver consists of

Plastic housing which accommodates the electronics

Mounting plate

RDD100.1RF

Description

Electromotoric actuator

Electrothermal actuator
(for radiator valve

Electrothermal actuator
(for small valve

Damper

Damper actuator

Damper

Rotary damper actuator

Operation and settings

RDD100.1RFS  Wireless room thermostat with LCD

room thermostat consists of 3 parts:

Plastic housing which accommodates the electronics, the operating
and the room temperature sensor
Mounting plate with screw terminals
Table stand

The housing engages in the mounting plate and is secured with a
The optional table stand snaps onto the rear of the mounting plate.

The RCR100RF receiver consists of 2 parts:

Plastic housing which accommodates the electronics
Mounting plate with screw terminals

RDD100.1RF

1)

Touchkey for o

2) Touchkey for increasing a value

3) Touchkey for decreasing a value

Description

Product No.

Electromotoric actuators

SFA21..

Electrothermal actuators
(for radiator valves)

STA23..

Electrothermal actuators
(for small valves 2.5 mm)

STP23..

Damper actuators

GDB..

Damper actuators

GSD..

Damper actuators

GQD..

Rotary damper actuators

GXD..

3 / 13

CB1N1424en

2017-11-21

Plastic housing which accommodates the electronics, the operating elements

is secured with a screw.

the mounting plate.

Touchkey for operating mode

for increasing a value

for decreasing a value

Product No.

Data Sheet

SFA21..

4863

STA23..

4884

STP23..

4884

GDB..

4634

GSD..

4603

GQD..

4604

GXD..

4622

Summary of Contents for RDD100.1RF

Page 1: ...gies RDD100 1RF RCR100RF Wireless room thermostat with LCD RDD100 1RFS or heating systems oom temperature control Comfort Economy and Protection mode position control with On Off control output Adjustable commissioning and control parameters attery powered room thermostat DC 3 V RDD100 1RF ains powered receiver AC 230 V RCR100RF Building Technologies 1424 RDD100 1RFS Adjustable commissioning and c...

Page 2: ...missioning and control parameters Standalone wireless transmitter and receiver Wireless operating frequency 433 MHz Temperature control The RDD100 1RFS acquires the room temperature with its built in sensor and maintains the setpoint by delivering control commands The switching differential is 1 K Q14 T C ON OFF W SD 1424D01 T Room temperature SD Switching differential W Room temperature setpoint ...

Page 3: ...temperature sensor Mounting plate with screw terminals Table stand The housing engages in the mounting plate and is secured with a The optional table stand snaps onto the rear of the mounting plate The RCR100RF receiver consists of 2 parts Plastic housing which accommodates the electronics Mounting plate with screw terminals RDD100 1RF 1 Touchkey for o 2 Touchkey for increasing a value 3 Touchkey ...

Page 4: ...cription Symbol Description 1 Indicating that batteries need to be replaced 7 Touchkey lock activated 2 Comfort mode 8 Display of zone default is 1 3 Economy mode 9 C Room temperature in degrees Celsius 4 Display of room temperature setpoint etc 10 Heating On 5 F Room temperature in degrees Fahrenheit 11 Current room temperature 6 Protection mode Protection mode icon can be enabled via parameter s...

Page 5: ...uipment microwaves etc Do not mount near larger metallic structures or constructional elements with fine metal meshes such as special glass or special concrete See Mounting Instructions CB1M1439xx enclosed with the thermostat Ensure that wiring protection and earthing comply with local regulations Correctly size the cables to the thermostat and the valve actuators Use only valve actuators rated fo...

Page 6: ...1 second From the calculation assuming 4 operations per day on the thermostat the estimated 1 second scanning rate results in a battery life of 1 year If the user increases the scanning rate the batteries life is extended If the battery symbol appears the batteries are almost exhausted and should be replaced Use alkaline batteries type AAA For the pairing process between transmitter and receiver r...

Page 7: ...en Comfort Economy and Protection mode is made by pressing touchkey When Comfort mode is activated symbol appears on the display The setpoint 20 ºC can be readjusted by pressing touchkeys and When Economy mode is activated symbol appears on the display The setpoint 16 ºC can be readjusted by pressing touchkeys and If the temperature falls below 5 ºC the thermostat automatically activates the heati...

Page 8: ...5 C WARNING Electrolyte leakage Chemical burns Only grasp damaged batteries using suitable protective gloves If electrolyte comes into contact with eyes immediately rinse eyes with plenty of water Consult a doctor Observe the following Only replace batteries with batteries of the same type and from the same manufacturer Observe the polarities The batteries must be new and free from damage Do not m...

Page 9: ...tions Temperature Humidity Mechanical conditions As per IEC 60721 3 2 Class 2K3 25 60 C 95 r h Class 2M2 Storage Climatic conditions Temperature Humidity As per IEC 60721 3 1 Class 1K3 25 60 C 95 r h EU Conformity CE CE1T1420xx RCM conformity CE1T1420en_C1 Safety class II as per EN 60730 1 EN 60730 2 9 Pollution class II as per EN 60730 1 Degree of protection of housing IP30 as per EN 60529 The pr...

Page 10: ...ection with max C 10 A circuit breaker in the supply lines required under all circumstances External protection for incoming cable Circuit breaker Circuit breaker tripping characteristic Max 10 A Type B C or D to EN 60898 60947 Contact life at AC 230 V A res Guide value 1 x 10 5 cycles Insulating strength Between relay contacts and coil Between relay contacts same pole AC 5 000 V AC 1 000 V Connec...

Page 11: ...tuating device L N AC 230 V Lx Nx AC 24 230 V Application examples T T F1 F2 N2 M1 Y2 1424S01 N1 T F1 F2 N2 M1 Y2 1424S02 T T T N1 Wireless room thermostat with receiver control of a gas fired wall hung boiler Wireless room thermostat with receiver control of a gas fired floor standing boiler Y1 1424S03 M1 N2 T N1 F1 Thermal reset limit thermostat F2 Safety limit thermostat M1 Circulating pump N1 ...

Page 12: ...mostat with LCD CB1N1424en Building Technologies 2017 11 21 Dimensions Room thermostat RDD100 1RF 85 106 39 8 25 5 83 5 4 1 7 1 21 5 0 5 82 93 1424M01 Ø80 Ø60 Receiver RCR100RF 7 1 4 1 83 5 0 5 27 5 84 103 2 Ø5 5 Ø80 Ø60 1424M02 Dimensions in mm ...

Page 13: ...017 11 21 Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 CH 6300 Zug Tel 41 58 724 24 24 Siemens Switzerland Ltd 2013 2017 Technical specifications and availability subject to change without notice www siemens com buildingtechnologies ...