Siemens
RDD100.1RFS
Building Technologies
Mounting and installation notes
Do not mount the thermostat in niches or bookshelves, not behind curtains, not
above or near heat sources, and not exposed to direct solar radiation. Mount
about 1.5 m above the floor.
Mounting
∂
Mount the
from heating/cooling
∂
Install the receiver close to the controlled un
∂
Choose the location to ensure largely interference
mounting the
,
Do not mount in a control panel
,
Do
,
Do not mount near electrical cables and equipment
microwaves, etc.
,
Do not mount near larger metallic structures or constructional elements with
fine metal meshes such as special glass or special concrete
Wiring
See Mounting I
∂
Ensure that wiring,
∂
Correctly
∂
Use only valve
∂
If the thermostat cannot accommodate all cables, power must be fed to the
system via an e
Warning!
No internal line protection for supply lines to external consumers.
Risk of fire and injury
∂
Adapt the line diameters as per local regulations to the rated value of the
installed overcurrent protection device.
∂
The AC 230
current of no more than 10 A
∂
Disconnect from
∂
Make sure the receiver is not c
RDD100.1RFS Wireless room thermostat with LCD
Do not mount the thermostat in niches or bookshelves, not behind curtains, not
above or near heat sources, and not exposed to direct solar radiation. Mount
about 1.5 m above the floor.
Mount the room thermostat in a clean and dry location
from heating/cooling equipment, and not exposed to drip or splash water
Install the receiver close to the controlled unit if possible
Choose the location to ensure largely interference-free reception.
mounting the receiver, observe the following:
Do not mount in a control panel
Do not mount on metallic surfaces
Do not mount near electrical cables and equipment
microwaves, etc.
Do not mount near larger metallic structures or constructional elements with
fine metal meshes such as special glass or special concrete
See Mounting Instructions CB1M1439xx enclosed with the thermostat.
Ensure that wiring, protection and earthing comply with local regulations
Correctly size the cables to the thermostat and the valve actuators
Use only valve actuators rated for AC 24… 230 V
If the thermostat cannot accommodate all cables, power must be fed to the
system via an external terminal block
Warning!
No internal line protection for supply lines to external consumers.
Risk of fire and injury due to short-circuits!
Adapt the line diameters as per local regulations to the rated value of the
installed overcurrent protection device.
The AC 230 V mains supply line must have a circuit breaker with a rat
current of no more than 10 A
Disconnect from power supply before removing the unit from its mounting plate
Make sure the receiver is not connected to power during
5 / 13
CB1N1424en
2017-11-21
Do not mount the thermostat in niches or bookshelves, not behind curtains, not
above or near heat sources, and not exposed to direct solar radiation. Mount it
thermostat in a clean and dry location without direct air flow
and not exposed to drip or splash water
it if possible
free reception. When
Do not mount near electrical cables and equipment such as PCs, TVs,
Do not mount near larger metallic structures or constructional elements with
fine metal meshes such as special glass or special concrete
enclosed with the thermostat.
and earthing comply with local regulations
thermostat and the valve actuators
If the thermostat cannot accommodate all cables, power must be fed to the
No internal line protection for supply lines to external consumers.
Adapt the line diameters as per local regulations to the rated value of the
circuit breaker with a rated
the unit from its mounting plate
onnected to power during wiring