A5E36197302
SmartLinx PROFIBUS DP-V1 – Operating Instructions
Page 13
m
m
m
m
m
A
pp
lic
ati
on
la
ye
r
Word 2: PV Point 1 Status Profi status
PV status byte.
7
PV Point 2 Signal Strength
The
3.2.9.4. Echo Strength
(in dB)
from Transducer 1. The value
range is from minimum -30
to maximum 99.
Word
2
3.2.9.4. Echo
Strength
8
PV Point 3 (Process variable for
Point 3) in Programmed units
Float
4
3.2.6.2. Reading
10
PV Point 3 Status Profi status
PV status byte. See next table for
more details.
Word
2
n/a
11
Digital inputs
The value of the digital inputs are
mapped into this Word. Bit 0 is
the Digital Input 1.
Word
2
2.9.2.3. Discrete
Input 1 Scaled
State
12
Relay outputs
The value of the relay outputs are
mapped into this Word. Bit 0 is
the Relay Output 1.
Word
2
13
mA input 1
The value of the analog input is
mapped into this Word.
Float
4
2.6.6. Raw mA Input
Value
15
Totalizer 1
References the Totalizer parame-
ter within the Siemens device.
UINT32
4
17
Totalizer 2
References the Totalizer parame-
ter within the Siemens device.
UINT32
4
Hexadecimal
number
Byte status
0x80
Good
0x10
Bad: malfunction
0x1f
Bad: out-of-service
Word
offset
Description
Data
type
Bytes
Parameter