Page 8
SmartLinx PROFIBUS DP-V1 – Operating Instructions
A5E36197302
m
m
m
m
m
O
pe
ra
tio
n
Error conditions of the red diagnostics light
1Hz – Error in configuration
Indicates that the I/O length variable set during initialization is not equal to the length set
during configuration of the network. See
Configuring the slave device on page 10 for
lengths supported by the SmartLinx module, and see your PLC documentation for setting
the I/O length variable.
2Hz – Error in user parameter data
Indicates that the length and / or contents of the user parameter data set during
initialization of the module is greater than the length and/or contents set during
configuration of the network. See
Configuring the slave device on page 10 for supported
lengths.
4Hz – Error in initialization
Consult your Siemens representative.