99 / 116
Siemens
Web server OZW672... V4.0
CE1C5712en
Building Technologies
Appendix
28.08.2012
7 Appendix
7.1 General
notes
Names of data points and message text, e.g. of faults, cannot contain special
characters or umlauts. Valid characters:
•
a…z and A…Z
•
0…9
•
! „ $ % & ‚ ( ) * + ` - . / : ; < = > ? "Space
When sent,
invalid characters
will be converted to "
?
"
(question marks).
7.2 Diagnostics
7.2.1
Web server fault codes
Fault code
Web server fault
General
0 No
fault
Communications
81
No bus power supply
1)
95
Invalid time of day
(Web server time not or incorrectly entered).
100
>1 clock time master
142
Device failure (Bus)
2)
171
[Fault input 1] fault
172
[Fault input 2] fault
438
Incorrect bus connected
439
Bus module not identified
448
Message receiver 1 not reached
3)
449
Message receiver 2 not reached
3)
450
Message receiver 3 not reached
3)
451
Message receiver 4 not reached
3)
System configuration errors
82
>1 identical device address
(Devices have same address).
1)
Device failure
monitoring (
Bus
) is stopped if the bus has no power.
2) Created by the web server for the device failed.
Device failure (Bus) as a result, device failure (bus) is assigned to "System faults",
whereas all other faults generated by the web server are assigned as "Local faults".
3) Possible causes of recipient type e-mail: Erroneous Ethernet or e-mail settings.
Text entry
Note
Fault codes