45 / 116
Siemens
Web server OZW672... V4.0
CE1C5712en
Building Technologies
Operate using a web browser
28.08.2012
The following information displays the current settings and states on the LPB / BSB
bus.
Path: Home > 0.5 OZW672… > Device information > LPB / BSB
Data point
Explanation, example
Connected bus
The web server autonomously identifies the bus
system connected. Possible values ---, LPB,
BSB.
Segment number
Part of the LPB device address.
Device number
Part of the LPB device address.
Clock time source
•
Autonomous
: Time/date is created from the
Quartz of the web server. No synchronization
with bus devices.
•
Slave with remote setting
: Web server re-
ceives time/date from master. The master
supplies both date and time on the web ser-
ver and is then sent to all bus devices.
•
Slave without rem setting
: Web server re-
ceives time/date from master. The web server
date/time setting is not sent to the master.
The master resets date/time.
•
Master
: Time/date is created from the Quartz
of the web server. The web server supplies
both date and time to all bus devices.
Recommended: Configure the web server as
Master and the bus device as slave with or
without remote setting.
Number of devices max Maximum possible number of devices monitored
by the web server on the LPB/BSB bus.
Number of devices
current
Actual number of devices monitored by the web
server on the LPB/BSB bus.
Last change
Time of last change to device list.
LPB / BSB