34 / 116
Siemens
Web server OZW672... V4.0
CE1C5712en
Building Technologies
Commissioning
28.08.2012
2.7 Functional
check
Connections must be tested if all settings were made to the web server as well as
to system devices.
A PC on the local network is used to test operations via LAN. The log in dialog
box must be displayed after entering the local IP address for the web server
(see Section 2.2.2).
We recommend using mobile participants with Internet access (Smart phone,
mobile phone) to test operation over the Internet. The login dialog box must be
displayed after entering the public IP address or plant domain (see Section 3).
Do the test if the web server is to send a message or system report via e-mail
for a fault.
The test is also carried out if message suppression is switched on.
Path: Home > 0.5 OZW672… > Settings > Message receiver
Data point
Explanation, example
Test message receiver
Default val:
---
Setting val:
Message receiver
1..4
Select a message receiver to test the con-
nection to the receiver.
—
System report sent
Display values: ---, Yes, No
The display changes from "
---
" to "Yes" after a
few seconds. Message sent successfully.
No: Message receiver not reached.
—
Cause
Display values:
---, Network cable, DNS setting,
Address mail server, Port number
mail server, E-mail address
receiver, Authentication mail
server. See the following table.
"Cause" displays the results of "System
report sent".
For "Yes" the cause is "---"
For "No" the cause is displayed.
The first fault is displayed for multiple faults.
—
Message inhibition
Display values: Yes, No
Shows the message suppression switch
setting (
8
) (see Section 1.2).
—
A specific cause can originate in different sources. The problem must be solved
accordingly.
Cause
Cause of error
Solution
--- No
error
---
Netzwork cable
No network cable or
no active network con-
nected.
Connect cable or active
network. LEDs must be lit
at Ethernet connection.
DNS setting
DNS server could not be
reached or no guaran-
teed network connection.
Check Setting DNS ser-
ver, Default gateway, or
network connection.
Table continued on next page
Test condition
LAN
Internet
Test message receiver
Note
Cause: Cause of error
and problem solution