4.3.2.2 Specification
No.
Name
Operating temperature
typ. / max.
Static activation
temperature
1
Differential activation
temperature
2
Differential activation
possible from:
[°C]
[°C]
∆
T [K]
[°C]
1
A1R
60 °C rate of rise
25 / 50
60
25
3
2
BR
80 °C rate of rise
40 / 65
80
29
30
3
A1S
60 °C maximum
25 / 50
60
–
–
4
BS
80
℃
Maximum
40 / 65
80
–
–
14
Application-specific parameter sets
15
1
Applicable with slow temperature increases <1 K/min.
2
Applicable with fast temperature increases of >10 K/min. When there is a slow
temperature increase of <10 K/min, this value rises by a few degrees.
All parameter sets apart from 14 and 15 comply with standard EN 54-5.