Planning
4
Compatibility
33
Building Technologies
A6V10367521_h_en_--
Fire Safety
2015-02-02
4 Planning
4.1 Compatibility
Compatible with control panels that support the C-NET-Ex detector line.
Additionally, the point detector OOH740-A9-Ex can be operated on a collective
detector line.
The table below shows the compatibility of the point detector with various control
panels:
Detector line
Control panel
FC20xx
FC72x
SIGMASYS
AlgoRex
C-NET-Ex
–
X
–
–
X = compatible
– = not compatible
You will find details in the 'List of compatibility'.
Note the information provided in document 001204 when using the detector in
collective mode.
See also
2
4.2 Ambient features
In selecting the optimum parameter set, the following factors must be taken into
account:
l
Risk of injury to persons
l
Concentration of valuable items
l
Room geometry
l
Deceptive phenomena
l
Risk of fire
l
Critical fire size
Risk of injury to persons
People's lives are severely at risk in venues such as concert halls, nursing homes,
and hospitals. The risk of injury to persons is therefore very high in such places. In
canteen kitchens the situation is different. Few people work in such facilities and
are able to save themselves in the event of timely alarms. The risk of injury to
persons is thus rather low in this case.
Concentration of valuable items
Irreplaceable cultural assets are often on display in museums. Computer centers
house servers with large data volumes. The concentration of valuable items is
rather high. In a normal hotel room the concentration of valuable items must be
classified as low.