4
Planning
Parameter sets for addressed operation
36
Building Technologies
A6V10367521_h_en_--
Fire Safety
2015-02-02
High Sensitive Fast (9):
This parameter set is suited for applications requiring very high sensitivity levels. It
reveals a significantly higher optical and thermal sensitivity than 'Fast Response'.
This parameter set is also suited for applications that can otherwise only be
covered with special detectors.
Download 1 (14) / download 2 (15):
Application-specific parameter sets that can be loaded on site (depending on the
control panel).
4.3.1.2 Use
No. Name
Risk of injury to
persons
Concentration
of valuable
items
Room
geometry
Deceptive
phenomena
Risk of fire
Critical fire size
small …
large
low …
high
simple …
complex
few …
many
small …
large
small …
medium
8
High
Suppression
5 Suppression
0
and
7
High
Compensation
2 Robust
4 Balanced
6 Fast
Response
9
High Sensitive
Fast
The 'High Suppression' and 'High Sensitive Fast' parameter sets are only suited
for special applications.