background image

5

+

+

_
_

1

2

3

4

TB2

1

2

3

4

TB3

+

_

1

2

3

4

TB2

1

2

3

4

TB3

INITIATING

DEVICE

CLASS B WIRING*

SUPERVISED, POWER LIMITED PER NEC 760

*OPERATES IN FULL COMFORMITY WITH STYLE 4

T-TAPPING ALLOWED

**OPERATES IN FULL COMFORMITY WITH STYLE 6

CLASS A WIRING**

SUPERVISED, POWER LIMITED PER NEC 760

NO

T-TAPPING

ALLOWED

JUMPERS ARE OPTIONAL

FOR MMB-3. REFER

TO CSG-M REV. 17.01

FOR CONFIGURATION.

Analog Device Loops 1 and 2
(TB2 and TB3)

These two ALD-2I loops each support up to 60
analog type devices.

To install a device for Class B, refer to Figure 6
and the electrical specifications.

To install a device for Class A, refer to Figure 6
and the electrical specifications.

Figure 6

Wiring the ALD-2I Analog Loops

R

E

W

O

P

V

4

2

Y

R

A

I

L

I

X

U

A

S

E

C

I

V

E

D

E

L

B

I

T

A

P

M

O

C

s

e

c

i

v

e

D

e

l

b

i

t

a

p

m

o

C

n

o

i

t

a

l

l

a

t

s

n

I

s

n

o

i

t

c

u

r

t

s

n

I

6

B

1

-

M

Z

C

7

-

5

5

3

5

9

0

-

5

1

3

N

/

P

6

B

-

P

C

I

8

-

6

0

3

5

9

0

-

5

1

3

N

/

P

6

1

-

D

O

M

7

-

0

3

8

0

9

0

-

5

1

3

N

/

P

7

-

I

O

M

7

-

9

9

7

2

9

0

-

5

1

3

N

/

P

A

5

-

S

P

8

-

7

6

3

2

9

0

-

5

1

3

N

/

P

7

N

5

-

S

P

2

1

-

9

2

7

2

9

0

-

5

1

3

N

/

P

C

5

-

/

5

-

B

K

M

3

-

7

2

7

8

4

0

-

5

1

3

N

/

P

C

6

-

/

6

-

B

K

M

4

-

2

2

7

8

4

0

-

5

1

3

N

/

P

C

F

3

-

/

C

-

/

F

3

-

/

3

-

C

C

R

6

-

5

6

6

8

4

0

-

5

1

3

N

/

P

t

h

g

i

n

K

t

n

e

li

S

9

2

1

5

/

8

2

1

5

5

-

4

9

2

3

9

0

-

5

1

3

N

/

P

5

3

-

R

S

8

-

1

9

6

7

8

0

-

5

1

3

N

/

P

D

4

-

/

D

3

-

/

D

2

-

H

D

S

D

8

-

/

D

7

-

/

D

6

-

/

D

5

-

/

3

-

1

8

4

9

4

0

-

5

1

3

N

/

P

1

-

S

N

§

3

-

9

0

4

5

8

0

-

5

1

3

N

/

P

§

n

o

i

t

i

d

E

h

t

8

4

6

8

L

U

r

e

p

d

e

t

s

i

L

Electrical Specifications for the Analog
Device Loops

1. Electrical ratings:

SUPERVISORY: 30 V unfiltered full wave

(peak), 30mA max

ALARM:

30 V unfiltered full wave
(peak), 30mA max
(60 devices in alarm)

2. All wiring must be in accordance with Article

760 of NEC or the local building codes. Refer
to Figure 6.

3. Only the list of devices in the 

Analog Device

Loops - Compatible Devices

 table may be

used. A maximum of 60 devices may be
connected to a single loop.

4. No end of line device is required.

5. Both circuits are power limited per NFPA 70,

NEC. Each detector, or group of detectors,
requires a two-wire circuit of 18 AWG
minimum. For additional wiring information,
refer to the Wiring Specification for MXL,
MXL-IQ and MXLV Systems, P/N 315-092772.

6. Total circuit resistance must not exceed 100

ohms.

Maximum capacitance:

0.4μF line to line
0.8μF line to ground

7. T-tapping is NOT allowed on Class A loops.

8. The jumpers shown in Figure 6 for Class B

wiring are optional. They are not required if the
proper settings are made in CSG-M Rev. 17.01
or higher.

Positive and negative ground fault detected at <40K ohms for TB2 (1-4) and TB3 (1-4).

Summary of Contents for MMB-3

Page 1: ...me battery voltage the AC voltage and the charger current on the MKB display It also has a 1 amp 24 VDC output that powers CZM 1 1B6 modules For additional information on the MXL MXLV System refer to the MXL MXLVManual P N 315 092036 INSTALLATION Remove all system power before installation first battery and then AC To power up connect the AC first then the battery Installing the MMB 3 Board Unpack...

Page 2: ...PS 6 8 AMP F4 MOM 4 15 AMP MMB 3 TB5 TB6 TB7 TB4 1 P18 P11 JP6 JP5 S2 P9 1 S1 TB9 3 1 2 P20 TB8 4 3 2 1 XNET _ _ _ _ _ _ _ _ _ _ _ C NC NO C NC NO C NC NO ALD 2I ALD 2I DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE F5 5V AUX 0 75 AMP 1 ALD GND FAULT DISCONNECT DS7 DS9 DS8 MMB GND FAULT MNET GND FAULT MNET XMIT P7 1 S4 3 S7 F6 BATTERY CHARGER 5 AMP TB10 4 3 2 1 EXPANSION DO NOT USE DO NOT ...

Page 3: ...he MMB 3 in this configuration IMPORTANT NOTE An MXL panel cannot have a NET 7 7M in the system and use the MNET Port TB1 on the MMB 3 Real Time Clock The second jumper on the MMB 3 is P17 which must be set for the real time clock to operate properly Move the jumper to the on position position 2 and 3 to provide backup battery power to the real time clock Internal Wiring To complete the MMB 3 inte...

Page 4: ...with the CZM 1 1B6 Remote Conventional Zone module Figure 4 shows Class B wiring Figure 5 shows Class A wiring The jumpers shown in Figure 4 are optional They are not required if the proper settings are made in CSG M Rev 17 01 or higher Class B wiring can be used to obtain the maxi mum of 20 CZM 1B6s Each Class B wire run can support a maximum of 10 CZM 1B6s 4 ohms max Multiple Class B power conne...

Page 5: ... 3 N P t h g i n K t n e l i S 9 2 1 5 8 2 1 5 5 4 9 2 3 9 0 5 1 3 N P 5 3 R S 8 1 9 6 7 8 0 5 1 3 N P D 4 D 3 D 2 H D S D 8 D 7 D 6 D 5 3 1 8 4 9 4 0 5 1 3 N P 1 S N 3 9 0 4 5 8 0 5 1 3 N P n o i t i d E h t 8 4 6 8 L U r e p d e t s i L Electrical Specifications for the Analog Device Loops 1 Electrical ratings SUPERVISORY 30 V unfiltered full wave peak 30mA max ALARM 30 V unfiltered full wave pe...

Page 6: ...M Z C 9 5 2 7 0 9 0 5 1 3 N P 6 B 1 M Z C 7 5 5 3 5 9 0 5 1 3 N P 1 1 T P F 1 1 P F B D h t i w S 3 B D T P D A 1 1 B D 0 1 1 2 9 5 9 0 5 1 3 N P 0 1 1 2 9 5 9 0 5 1 3 N P H I 0 6 I 0 6 D I S R 3 X B D S 3 B D 2 7 8 2 0 9 0 5 1 3 N P H A I 0 6 A I 0 6 D I S R 3 X B D S 3 B D 2 7 8 2 0 9 0 5 1 3 N P H B I 0 6 B I 0 6 D I I 3 D A I R X 3 D A 6 4 3 2 3 9 0 5 1 3 N P 5 5 3 2 3 9 0 5 1 3 N P H 1 1 I L ...

Page 7: ...for wiring connections Use only with power limited Class 2 circuits Common Trouble Relay The trouble relay changes state whenever a System trouble is detected The relay is rated for 2A 30 VDC 120 VAC resistive Refer to Figure 8 for the wiring connections Use only with power limited Class 2 circuits NOTE This relay is normally energized 9 8 7 6 5 4 3 2 1 TB4 SUPERVISORY TROUBLE ALARM RATINGS 2A 30 ...

Page 8: ...P MAX CURRENT 150mA TERMINATE THE SHIELD AT THE MMB 3 CHASSIS ONLY Figure 9 Style 4 Network MNET Figure 10 Style 7 Network MNET 1 2 3 4 1 1 2 2 1 2 3 3 4 4 TB1 TB4 TB4 TB1 MMB 3 MOI 7 PSR 1 PSR 1 EOLR 120 OHMS 1 4W 5 P N 140 049099 CHASSIS SHIELD NO EOLR EOLR 120 OHMS 1 4W 5 P N 140 820150 18 AWG MIN 5000 FEET MAX USE TWISTED PAIR OR SHIELDED TWISTED PAIR POWER LIMITED TO NFPA 70 PER NEC 760 MAX V...

Reviews: