background image

3

2. Secure in place using the hardware provided.

Be sure the screws and nuts are tight, as they pro-
vide the earth ground connection for the MMB-3.

3. Place the removable terminal blocks from

Hardware kit P/N 545-649036 on the
appropriate terminals and secure in place.

CONFIGURATION

The MMB-3 has two jumpers—jumper P7 for
MNET and jumper P17 for Real Time clock—
which must be set for proper operation. Refer to
Figure 2 for the location of the jumpers.

MNET

To configure the MNET port (TB1) for either Style
4 or Style 7 operation, set jumper P7 on the
MMB-3 to one of the four settings listed below
that is applicable to your system configuration.

1. If the MNET port (TB1) is not being used on

the MMB-3 and there is no NET-7/7M in the
system configuration, then set the jumper to
positions 1 and 2.

2. If the MNET port (TB1) is configured as Style

4, then set the jumper to positions 1 and 2.

3. If the MNET port is (TB1) configured as Style

7, then set the jumper to positions 1 and 2.
Remember to update 

MMB-3 MNET STYLE 7

in the CSGM to display 

YES

. Configurations 1,

2, and 4 should be set to 

NO

.

NOTE:

In settings 1-3, the user can upload a
CSG-M configuration in the customary
method through P5 (To Programmer).

4. If you are not using the MNET port, but are using

a NET-7/7M in your MMB-3 configuration, then
set the jumper to positions 2 and 3.

NOTE:

If setting 4 is used, the CSG-M
configuration MUST uploaded
through P1 on any NET-7/7M that is
on the Style 7 MNET. You cannot
upload a CSG-M configuration
through P5 on the MMB-3 in this
configuration.

IMPORTANT NOTE

An MXL panel cannot have a NET-7/7M in
the system and use the MNET Port (TB1)
on the MMB-3.

Real Time Clock

The second jumper on the MMB-3 is P17 which
must be set for the real time clock to operate
properly.

• Move the jumper to the 

on 

position (position 2

and 3) to provide backup battery power to the
real time clock.

Internal Wiring

To complete the MMB-3 internal wiring connec-
tions, follow the steps below, skipping those that
do not apply to your MXL System.

1. Main Power Connections

Primary power for the MMB-3 is provided by
the MPS-6 or MPS-12. Both of these mount
in the lower right-hand corner of the MXL
enclosure. Follow the instructions below for
the appropriate power supply.

MPS-6

 — 

Install the MPS-6 (See MPS-6

Instructions, P/N 315-090334). With the AC
mains disconnected, connect the MPS-6
power cable to P1 of the MMB-3. 

Be sure

that the jumper assembly is installed in
P14 of the MMB-3. If this jumper is not
installed, the MMB-3 will detect a
permanent AC fail or indicate auxiliary
power voltage is low.

MPS-12

 — 

Install the MPS-12 (See MPS-12

Instructions, P/N 315-092030). Remove and
discard the jumper assembly installed in P14
of the MMB-3. Disconnect the AC mains.
Connect the MPS-12 power cable to P14 of
MMB-3.

2. Battery Power Connection

The MMB-3 kit includes a battery cable
(wiring harness). Use the harness to connect
the 24V backup batteries to P2 of MMB-3.

3. MOM-4 Optional Module Card Cage

There are two connections between the
MMB-3 and the MOM-4 board.

a. The first is the 24V power connection.

P3 provides backward compatibility with the
MMB-1 and should only be used when
replacing an MMB-1. P3 is limited to 2
amps. The MMB-3 allows the use of either

Summary of Contents for MMB-3

Page 1: ...me battery voltage the AC voltage and the charger current on the MKB display It also has a 1 amp 24 VDC output that powers CZM 1 1B6 modules For additional information on the MXL MXLV System refer to the MXL MXLVManual P N 315 092036 INSTALLATION Remove all system power before installation first battery and then AC To power up connect the AC first then the battery Installing the MMB 3 Board Unpack...

Page 2: ...PS 6 8 AMP F4 MOM 4 15 AMP MMB 3 TB5 TB6 TB7 TB4 1 P18 P11 JP6 JP5 S2 P9 1 S1 TB9 3 1 2 P20 TB8 4 3 2 1 XNET _ _ _ _ _ _ _ _ _ _ _ C NC NO C NC NO C NC NO ALD 2I ALD 2I DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE F5 5V AUX 0 75 AMP 1 ALD GND FAULT DISCONNECT DS7 DS9 DS8 MMB GND FAULT MNET GND FAULT MNET XMIT P7 1 S4 3 S7 F6 BATTERY CHARGER 5 AMP TB10 4 3 2 1 EXPANSION DO NOT USE DO NOT ...

Page 3: ...he MMB 3 in this configuration IMPORTANT NOTE An MXL panel cannot have a NET 7 7M in the system and use the MNET Port TB1 on the MMB 3 Real Time Clock The second jumper on the MMB 3 is P17 which must be set for the real time clock to operate properly Move the jumper to the on position position 2 and 3 to provide backup battery power to the real time clock Internal Wiring To complete the MMB 3 inte...

Page 4: ...with the CZM 1 1B6 Remote Conventional Zone module Figure 4 shows Class B wiring Figure 5 shows Class A wiring The jumpers shown in Figure 4 are optional They are not required if the proper settings are made in CSG M Rev 17 01 or higher Class B wiring can be used to obtain the maxi mum of 20 CZM 1B6s Each Class B wire run can support a maximum of 10 CZM 1B6s 4 ohms max Multiple Class B power conne...

Page 5: ... 3 N P t h g i n K t n e l i S 9 2 1 5 8 2 1 5 5 4 9 2 3 9 0 5 1 3 N P 5 3 R S 8 1 9 6 7 8 0 5 1 3 N P D 4 D 3 D 2 H D S D 8 D 7 D 6 D 5 3 1 8 4 9 4 0 5 1 3 N P 1 S N 3 9 0 4 5 8 0 5 1 3 N P n o i t i d E h t 8 4 6 8 L U r e p d e t s i L Electrical Specifications for the Analog Device Loops 1 Electrical ratings SUPERVISORY 30 V unfiltered full wave peak 30mA max ALARM 30 V unfiltered full wave pe...

Page 6: ...M Z C 9 5 2 7 0 9 0 5 1 3 N P 6 B 1 M Z C 7 5 5 3 5 9 0 5 1 3 N P 1 1 T P F 1 1 P F B D h t i w S 3 B D T P D A 1 1 B D 0 1 1 2 9 5 9 0 5 1 3 N P 0 1 1 2 9 5 9 0 5 1 3 N P H I 0 6 I 0 6 D I S R 3 X B D S 3 B D 2 7 8 2 0 9 0 5 1 3 N P H A I 0 6 A I 0 6 D I S R 3 X B D S 3 B D 2 7 8 2 0 9 0 5 1 3 N P H B I 0 6 B I 0 6 D I I 3 D A I R X 3 D A 6 4 3 2 3 9 0 5 1 3 N P 5 5 3 2 3 9 0 5 1 3 N P H 1 1 I L ...

Page 7: ...for wiring connections Use only with power limited Class 2 circuits Common Trouble Relay The trouble relay changes state whenever a System trouble is detected The relay is rated for 2A 30 VDC 120 VAC resistive Refer to Figure 8 for the wiring connections Use only with power limited Class 2 circuits NOTE This relay is normally energized 9 8 7 6 5 4 3 2 1 TB4 SUPERVISORY TROUBLE ALARM RATINGS 2A 30 ...

Page 8: ...P MAX CURRENT 150mA TERMINATE THE SHIELD AT THE MMB 3 CHASSIS ONLY Figure 9 Style 4 Network MNET Figure 10 Style 7 Network MNET 1 2 3 4 1 1 2 2 1 2 3 3 4 4 TB1 TB4 TB4 TB1 MMB 3 MOI 7 PSR 1 PSR 1 EOLR 120 OHMS 1 4W 5 P N 140 049099 CHASSIS SHIELD NO EOLR EOLR 120 OHMS 1 4W 5 P N 140 820150 18 AWG MIN 5000 FEET MAX USE TWISTED PAIR OR SHIELDED TWISTED PAIR POWER LIMITED TO NFPA 70 PER NEC 760 MAX V...

Reviews: