Siemens MMB-3 Installation Instructions Manual Download Page 8

P/N 315-048860-7

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

1

2

3

4

1

1

2

2

1

2

3

3

4

4

TB1

TB4

TB4

TB1

MMB-3

MOI-1/7

PSR-1

PSR-1

RES EOL ASSEMBLY

120 OHMS, 1/4W, 5%

P/N 140-049099

CHASSIS

SHIELD

NO

EOLR

NO

EOLR

EOLR 120 OHMS,

1/4W, 5%

P/N 140-820150

NETWORK
NETWORK

18 AWG MIN

5000 FEET MAX

USE TWISTED PAIR OR

SHIELDED TWISTED PAIR

POWER LIMITED TO

NFPA 70 PER NEC 760

MAX VOLTAGE: 8V P-P

MAX CURRENT: 150mA

TERMINATE THE SHIELD AT

THE MMB-3 CHASSIS ONLY

Figure 9

Style 4 Network (MNET)

Figure 10

Style 7 Network (MNET)

1

2

3

4

1

1

2

2

1

2

3

3

4

4

TB1

TB4

TB4

TB1

MMB-3

MOI-7

PSR-1

PSR-1

EOLR 120 OHMS,

1/4W, 5%

P/N 140-049099

CHASSIS

SHIELD

NO

EOLR

EOLR 120 OHMS,

1/4W, 5%

P/N 140-820150

18 AWG MIN

5000 FEET MAX

USE TWISTED PAIR OR

SHIELDED TWISTED PAIR

POWER LIMITED TO

NFPA 70 PER NEC 760

MAX VOLTAGE: 8V P-P

MAX CURRENT: 150mA

TERMINATE THE SHIELD AT

THE MMB-3 CHASSIS ONLY

3

4

NO

EOLR

NO

EOLR

NO

EOLR

Positive and negative ground fault

detected at <20K ohms for TB1(1-4).

Positive and negative ground fault

detected at <20K ohms for TB1(1-4).

SET "MMB-3 MNET STYLE 7"

TO "NO" IN THE CSGM.

SET "MMB-3 MNET STYLE

7" TO "YES" IN THE CSGM.

Summary of Contents for MMB-3

Page 1: ...me battery voltage the AC voltage and the charger current on the MKB display It also has a 1 amp 24 VDC output that powers CZM 1 1B6 modules For additional information on the MXL MXLV System refer to the MXL MXLVManual P N 315 092036 INSTALLATION Remove all system power before installation first battery and then AC To power up connect the AC first then the battery Installing the MMB 3 Board Unpack...

Page 2: ...PS 6 8 AMP F4 MOM 4 15 AMP MMB 3 TB5 TB6 TB7 TB4 1 P18 P11 JP6 JP5 S2 P9 1 S1 TB9 3 1 2 P20 TB8 4 3 2 1 XNET _ _ _ _ _ _ _ _ _ _ _ C NC NO C NC NO C NC NO ALD 2I ALD 2I DO NOT USE DO NOT USE DO NOT USE DO NOT USE DO NOT USE F5 5V AUX 0 75 AMP 1 ALD GND FAULT DISCONNECT DS7 DS9 DS8 MMB GND FAULT MNET GND FAULT MNET XMIT P7 1 S4 3 S7 F6 BATTERY CHARGER 5 AMP TB10 4 3 2 1 EXPANSION DO NOT USE DO NOT ...

Page 3: ...he MMB 3 in this configuration IMPORTANT NOTE An MXL panel cannot have a NET 7 7M in the system and use the MNET Port TB1 on the MMB 3 Real Time Clock The second jumper on the MMB 3 is P17 which must be set for the real time clock to operate properly Move the jumper to the on position position 2 and 3 to provide backup battery power to the real time clock Internal Wiring To complete the MMB 3 inte...

Page 4: ...with the CZM 1 1B6 Remote Conventional Zone module Figure 4 shows Class B wiring Figure 5 shows Class A wiring The jumpers shown in Figure 4 are optional They are not required if the proper settings are made in CSG M Rev 17 01 or higher Class B wiring can be used to obtain the maxi mum of 20 CZM 1B6s Each Class B wire run can support a maximum of 10 CZM 1B6s 4 ohms max Multiple Class B power conne...

Page 5: ... 3 N P t h g i n K t n e l i S 9 2 1 5 8 2 1 5 5 4 9 2 3 9 0 5 1 3 N P 5 3 R S 8 1 9 6 7 8 0 5 1 3 N P D 4 D 3 D 2 H D S D 8 D 7 D 6 D 5 3 1 8 4 9 4 0 5 1 3 N P 1 S N 3 9 0 4 5 8 0 5 1 3 N P n o i t i d E h t 8 4 6 8 L U r e p d e t s i L Electrical Specifications for the Analog Device Loops 1 Electrical ratings SUPERVISORY 30 V unfiltered full wave peak 30mA max ALARM 30 V unfiltered full wave pe...

Page 6: ...M Z C 9 5 2 7 0 9 0 5 1 3 N P 6 B 1 M Z C 7 5 5 3 5 9 0 5 1 3 N P 1 1 T P F 1 1 P F B D h t i w S 3 B D T P D A 1 1 B D 0 1 1 2 9 5 9 0 5 1 3 N P 0 1 1 2 9 5 9 0 5 1 3 N P H I 0 6 I 0 6 D I S R 3 X B D S 3 B D 2 7 8 2 0 9 0 5 1 3 N P H A I 0 6 A I 0 6 D I S R 3 X B D S 3 B D 2 7 8 2 0 9 0 5 1 3 N P H B I 0 6 B I 0 6 D I I 3 D A I R X 3 D A 6 4 3 2 3 9 0 5 1 3 N P 5 5 3 2 3 9 0 5 1 3 N P H 1 1 I L ...

Page 7: ...for wiring connections Use only with power limited Class 2 circuits Common Trouble Relay The trouble relay changes state whenever a System trouble is detected The relay is rated for 2A 30 VDC 120 VAC resistive Refer to Figure 8 for the wiring connections Use only with power limited Class 2 circuits NOTE This relay is normally energized 9 8 7 6 5 4 3 2 1 TB4 SUPERVISORY TROUBLE ALARM RATINGS 2A 30 ...

Page 8: ...P MAX CURRENT 150mA TERMINATE THE SHIELD AT THE MMB 3 CHASSIS ONLY Figure 9 Style 4 Network MNET Figure 10 Style 7 Network MNET 1 2 3 4 1 1 2 2 1 2 3 3 4 4 TB1 TB4 TB4 TB1 MMB 3 MOI 7 PSR 1 PSR 1 EOLR 120 OHMS 1 4W 5 P N 140 049099 CHASSIS SHIELD NO EOLR EOLR 120 OHMS 1 4W 5 P N 140 820150 18 AWG MIN 5000 FEET MAX USE TWISTED PAIR OR SHIELDED TWISTED PAIR POWER LIMITED TO NFPA 70 PER NEC 760 MAX V...

Reviews: