24
5
Band, VRC, VLC status
6 Tap
Position
7 Load
Current
8 Load
Voltage
9
Load Voltage (primary)
10 Source
Voltage
11
Source Voltage (primary)
12 KVA
13 KVAR
14 KW
15 Power
Factor
Analog Outputs
Point #
Description
0
Op Count Total
8.2.5
Simple
Binary Inputs
Point #
Description
0
Auto Inhibit Status
1
Remote Switch position
2
Manual Switch position
Binary Outputs
Point #
Description
0 Tap
Raise
1 Tap
Lower
2
Auto Inhibit (On/Off)
Analog Inputs
Point #
Description
0 Tap
Position
1 Load
Voltage
2 Load
Current
3 Source
Voltage
Analog Outputs
No Analog Outputs in the Simple set currently.
8.2.6
Metering
Binary Inputs
Point #
Description
0
LOW Voltage Limiting, [1=On]
1
HIGH Voltage Limiting, [1=On]
2
Automatic Operation, [1=Inhibited]
3
Power Flow Direction, [0=Fwd, 1=Rev]
4
R/A/M Switch, [0=Off/Manual, 1=Auto/Remote]
5
Voltage Reduction Input 1, [0=Open, 1=Closed]
6
Voltage Reduction Input 2, [0=Open, 1=Closed]
7
Supervisory Switch, [0=Off, 1=On (Remote)]
8
Neutral Position Status, [0=inactive, 1=active]
9
Low Battery Status, [0=inactive, 1=active]
10
Raise Limit Reached, [0=inactive, 1=active]
11
Lower Limit Reached, [0=inactive, 1=active]