MJ-4 Communications Module
25
Binary Outputs
Point #
Description
0
Control Raise (1=raise)
1
Control Lower (1=lower)
2
Remote Auto/Manual (1=block)
3
Fwd Voltage Level (+/-.1V) (0=dec, 1=inc)
4
Bandwidth Voltage (+/-.1V) (0=dec, 1=inc)
5
Fwd Time Delay (+/- 5s) (0=dec, 1=inc)
6
Fwd Reactive Comp (+/- 1V) (0=dec, 1=inc)
7
Local Voltage Reduct (1=Active)
8
Remote Volt Reduct (1=Active)
9
Local Volt Reduct % (+/-.5V) (0=dec, 1=inc)
10
Remote Volt Red. % (+/-.5V) (0=dec, 1=inc)
11
Fwd Resistive Comp (+/- 1V) (0=dec, 1=inc)
12
Reset Demands & min/max (AI 20-26)
13
Reset Energies (AI 27-28)
Analog Inputs
Point #
Description
0
Operations Counter (100's)
1
Operations Counter (10's and 1's)
2 kVA
Load
3 kW
Load
4
Hardware Status (0=All Good)
5
Primary Load Current in Amps
6
Secondary Load Voltage
7
Primary Load Voltage
8
Primary Source Voltage
9 kVAR
Load
10 Power
Factor
11
Compensated Voltage (Sec.)
12
% Voltage Reduction in Effect
13 Tap
Position
14
Voltage Reduction Status
15
Voltage Limit Status
16
Tap Control Mode Status
17
R/A/M switch position
18
Load Voltage Harmonics %
19
Load Current Harmonics %
20
Fwd Voltage Level Setting
21
Fwd Bandwidth Setting
22
Fwd Time Delay Setting
23
Fwd Reactive Compensation
24
Local Voltage Reduction %
25
Remote Voltage Reduction %
26
Fwd Resistive Compensation
27
Load Current Demand (fwd. max.)
28
KVAR Load Demand (fwd. min.)
29
KVAR Load Demand (fwd. max.)
30
KW Load Demand (fwd. max.)
31
Load Voltage Inst. Fwd. Min
32
Load Voltage Inst. Fwd. Max
33
Load Current Inst. Fwd. Max
34
KWHR Forward (0-999)
35
MWHR Forward (0-999)