6. SYSTEM PARAMETERS
English
Parameter Function
Range
[Default]
Description / Notes
© Siemens plc 1999
G85139-H1751-U529-D1
49
4/8/99
P045
Inversion fixed setpoints for
fixed frequencies 1 - 4
0 - 7
[0]
Sets the direction of rotation for the fixed frequency:
FF 1
FF 2
FF3
FF 4
P045 = 0
Þ
Þ
Þ
Þ
P045 = 1
Ü
Þ
Þ
Þ
P045 = 2
Þ
Ü
Þ
Þ
P045 = 3
Þ
Þ
Ü
Þ
P045 = 4
Þ
Þ
Þ
Ü
P045 = 5
Ü
Ü
Þ
Þ
P045 = 6
Ü
Ü
Ü
Þ
P045 = 7
Ü
Ü
Ü
Ü
Þ
Fixed setpoints not inverted.
Ü
Fixed setpoints inverted.
P046
·
Fixed frequency 5 (Hz)
0 - 650.00
[25.0]
Valid if P006 = 2 and P051 = 6 or 18. , or P053-55=17
P047
·
Fixed frequency 6 (Hz)
0 - 650.00
[30.0]
Valid if P006 = 2 and P356 = 6 or 18, or P053-55=17
P048
·
Fixed frequency 7 (Hz)
0 - 650.00
[35.0]
Valid if P006 = 2, and P053-55=17
P049
·
Fixed frequency 8 (Hz)
0 - 650.00
[40.0]
Valid if P006 = 2, and P053-55=17
P050
Inversion fixed setpoints for
fixed frequencies 5 - 8
0 - 7
[0]
Sets the direction of rotation for the fixed frequency:
FF 5
FF 6
FF7
FF8
P050 = 0
Þ
Þ
Þ
Þ
P050 = 1
Ü
Þ
Þ
Þ
P050 = 2
Þ
Ü
Þ
Þ
P050 = 3
Þ
Þ
Ü
Þ
P050 = 4
Þ
Þ
Þ
Ü
P050 = 5
Ü
Ü
Þ
Þ
P050 = 6
Ü
Ü
Ü
Þ
P050 = 7
Ü
Ü
Ü
Ü
Þ
Fixed setpoints not inverted
Ü