English
9. SUPPLEMENTARY INFORMATION
G85139-H1751-U529-D1
© Siemens plc 1999
4/8/99
74
Filter Part Numbers:
Inverter Model No.
Class A Filter Part No.
Class B Filter Part No.
Standard
MMV12 - MMV300
Built-in
EN 55011 / EN 55022
MMV220F - MMV750F
Built-in
EN 55011 / EN 55022
MMV12/2 - MMV25/2
6SE3290-0BA87-0FB0
EN 55011 / EN 55022
MMV37/2 - MMV75/2
6SE3290-0BA87-0FB2
EN 55011 / EN 55022
MMV110/2 - MMV150/2
6SE3290-0BB87-0FB4
EN 55011 / EN 55022
MMV220/2 - MMV300/2
6SE3290-0BC87-0FB4
EN 55011 / EN 55022
MMV37/3 - MMV150/3
6SE3290-0DA87- 0FA1
6SE3290-0DA87-0FB1
EN 55011 / EN 55022
MMV220/3 - MMV300/3
6SE3290-0DB87- 0FA3
6SE3290-0DB87-0FB3
EN 55011 / EN 55022
MMV400/3 - MMV750/3
6SE3290-0DC87- 0FA4
6SE3290-0DC87-0FB4
EN 55011 / EN 55022
MDV550/2
6SE3290-0DG87- 0FA5
6SE2100-1FC20
EN 55011 / EN 55022
MDV750/2
6SE3290-0DH87- 0FA5
6SE2100-1FC20
EN 55011 / EN 55022
MDV1100/2 - MDV1850/2
6SE3290-0DJ87- 0FA6
6SE2100-1FC21
EN 55011 / EN 55022
MDV2200/2
6SE3290-0DJ87- 0FA6
EN 55011 / EN 55022
MDV3000/2 - MDV4500/2
6SE3290-0DK87- 0FA7
EN 55011 / EN 55022
MDV 750/3 - MDV1100/3
6SE3290-0DG87- 0FA5
6SE2100-1FC20
EN 55011 / EN 55022
MDV1500/3 - MDV1850/3
6SE3290-0DH87- 0FA5
6SE2100-1FC20
EN 55011 / EN 55022
MDV2200/3 - MDV3700/3
6SE3290-0DJ87- 0FA6
6SE2100-1FC21
EN 55011 / EN 55022
MDV4500/3 - MDV7500/3
6SE3290-0DK87- 0FA7
EN 55011 / EN 55022
Note: Maximum mains supply voltage when filters are fitted is 460V.
Three classes of EMC performance are available as detailed below. Note that these levels of performance are only achieved when using the
default switching frequency (or less) and a maximum motor cable length of 25 m.
Class 1: General Industrial
Compliance with the EMC Product Standard for Power Drive Systems EN 61800-3 for use in
Second Environment (Industrial)
and
Restricted Distribution
.
EMC Phenomenon
Standard
Level
Emissions:
Radiated Emissions
EN 55011
Level A1 *
Conducted Emissions
EN 61800 - 3
*
Immunity:
Electrostatic Discharge
EN 61000-4-2
8 kV air discharge
Burst Interference
EN 61000-4-4
2 kV power cables, 1 kV control
Radio Frequency Electromagnetic Field
IEC 1000-4-3
26-1000 MHz, 10 V/m
*
Emission limits not applicable inside a plant where
no other consumers are connected to the same
electricity supply transformer.