5. SYSTEM PARAMETERS
English
Parameter Function
Range
[Default]
Description / Notes
© Siemens plc 1999
G85139-H1750-U049-C1
37
19/08/99
P139
Peak output current detect
0.0 - 99.9
[-]
Stores the peak current seen by the motor. Can be reset using
∆
and
∇
buttons.
P140
Most recent fault code
0 - 9999
[-]
Read only. The last recorded fault code (see section 6) is stored in this
parameter. The stored value can be cleared by using the
∇
button .
Or by resetting to factory defaults (P944)
This is a copy of the code stored in P930.
P141
Most recent fault code -1
0 - 9999
[-]
This parameter stores the last recorded fault code prior to that stored
in P140/P930.
P142
Most recent fault code -2
0 - 9999
[-]
This parameter stores the last recorded fault code prior to that stored
in P141.
P143
Most recent fault code -3
0 - 9999
[-]
This parameter stores the last recorded fault code prior to that stored
in P142.
P201
Closed loop mode
0 - 2
[0]
0
= Normal operation (closed loop control disabled).
1
=
Not used.
2
= Closed loop control using analogue input for transducer feedback
input.
P202
••••
P
gain (%)
0.0 - 999.9
[1.0]
Proportional gain.
P203
••••
I
gain (%)
0.00 -
99.99
[0.00]
Integral gain.
0.01% corresponds to the longest integral action time.
P205
••••
Sample interval (x 25 ms)
1 - 2400
[1]
Sampling interval of feedback sensor. The integral response rate is
slowed down by this factor
P206
••••
Transducer filtering
0 - 255
[0]
0
=
Filter off.
1
-
255
= Low pass filtering applied to sensor.
P207
••••
Integral capture range (%)
0 - 100
[100]
Percentage error above which integral term is reset to zero.
P208
Transducer type
0 - 1
[0]
0
= An increase in motor speed causes an increase in sensor
voltage/current output.
1
= An increase in motor speed causes a decrease in sensor
voltage/current output.
P210
Transducer reading (%)
0.0 - 100.0
[-]
Read only. Value is a percentage of full scale of the selected input.
P211
••••
0% setpoint
0.00-
100.00
[0.00]
Value of P210 to be maintained for 0% setpoint.
P212
••••
100% setpoint
0.00-
100.00
[100.00]
Value of P210 to be maintained for 100% setpoint.
P220
PI frequency cut-off
0 - 1
[0]
0 =
Normal operation
1 =
Switch off inverter output at or below minimum frequency.
Note: Active in all modes.
P700
P701
••••
P702
P880
P900 to
P970
(Other than those listed below)
Specific to PROFIBUS-DP and CANbus operation. See PROFIBUS
or CANbus Handbook for further details.
Access only possible with P099 = 1 or 2
Specific to PROFIBUS-DP. See PROFIBUS Handbook for further details.
Access only possible with P099 = 1