230 V Single Phase MICROMASTER Inverters
Order No. (
6SE92
..)
10-7BA40
11-5BA40
12-1BA40
12-8BA40
13-6BA40
15-2BB40
16-8BB40
21-0BC40
21-3BC40
Inverter model
MM12
MM25
MM37
MM55
MM75
MM110
MM150
MM220
MM300
c
Input voltage range
1 AC 208V - 240 V +/-10%
Motor output rating a
(kW / hp)
0.12 /
1/
6
0.25 /
1/
3
0.37 /
1/
2
0.55 /
3/
4
0.75 / 1
1.1 / 1
1/
2
1.5 / 2
2.2 / 3
3.0 / 4
Continuous output
350 VA
660 VA
920 VA
1.14 kVA
1.5 kVA
2.1 kVA
2.8 kVA
4.0 kVA
5.2 kVA
Output current (nom.) a
0.75 A
1.5 A
2.1 A
2.6 A
3.5 A
4.8 A
6.6 A
9.0 A
11.8 A
Output current (max. continuous)
0.9 A
1.7 A
2.3 A
3.0 A
3.9 A
5.5 A
7.4 A
10.4 A
13.6 A
Input current (
I
rms)
1.8 A
3.2 A
4.6 A
6.2 A
8.2 A
11.0 A
14.4 A
20.2 A
28.3 A
Recommended mains fuse
10 A
16 A
20 A
25 A
32 A
Recommended lead
Input
1.0 mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
cross-section (min.)
Output
1.0 mm
2
1.5 mm
2
2.5 mm
2
Dimensions (mm) (w x h x d)
73 x 175 x 141
149 x 184 x 172
185 x 215 x 195
Weight (kg / lb)
0.85 / 1.9
2.6 / 5.7
5.0 / 11.0
All 1 AC 230 V MICROMASTERS include integrated Class A filters. Optional external Class B filters are available (see section 8.3).
230 V 3 Phase MICROMASTER Inverters
Order No. (
6SE92
..)
10-7CA40 11-5CA40 12-1CA40 12-8CA40 13-6CA40 15-2CB40 16-8CB40 21-0CC40
21-3CC40
21-8CC13
Inverter model
MM12/2
MM25/2
MM37/2
MM55/2
MM75/2
MM110/2 MM150/2 MM220/2
MM300/2 c
MM400/2
Input voltage range
1 - 3 AC 208V - 240 V +/-10%
3 AC
Motor output rating a
(kW / hp)
0.12 /
1/
6
0.25 /
1/
3
0.37 /
1/
2
0.55 /
3/
4
0.75 / 1
1.1 / 1
1/
2
1.5 / 2
2.2 / 3
3.0 / 4
4.0 / 5
Continuous output
350 VA
660 VA
920 VA
1.14 kVA
1.5 kVA
2.1 kVA
2.8 kVA
4.0 kVA
5.2 kVA
7.0 kVA
Output current (nom.) a
0.75 A
1.5 A
2.1 A
2.6 A
3.5 A
4.8 A
6.6A
9.0 A
11.8 A
15.9 A
Output current (max. continuous)
0.9 A
1.7 A
2.3 A
3.0 A
3.9 A
5.5 A
7.4 A
10.4 A
13.6 A
17.5 A
Input current (
I
rms) (1 AC / 3 AC)
1.8 / 1.1 A 3.2 / 1.9 A 4.6 / 2.7 A 6.2 / 3.6 A 8.2 / 4.7 A 11.0 / 6.4 A 14.4 / 8.3 A 20.2 / 11.7 A
28.3 / 16.3 A
- / 21.1 A
Recommended mains fuse b
10 A
16 A
20 A
25 A
Recommended lead
Input
1.0 mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
cross-section (min.)
Output
1.0 mm
2
1.5 mm
2
2.5 mm
2
Dimensions (mm) (w x h x d)
73 x 175 x 141
149 x 184 x 172
185 x 215 x 195
Weight (kg / lb)
0.75 / 1.7
2.4 / 5.3
4.8 / 10.5
All 1 AC and 3 AC 230 V MICROMASTERS (excluding MM400/2) are suitable for 208 V operation.
All 3 AC 230 V MICROMASTERS can operate on 1 AC 230 V (MM300/2 requires an external line choke, e.g. 4EM6100-3CB).
380 V - 500 V Three Phase MICROMASTER Inverters
Order No. (
6SE92
..)
11-1DA40 11-4DA40 12-0DA40 12-7DA40 14-0DA40 15-8DB40 17-3DB40 21-0DC40 21-3DC40 21-5DC40
Inverter model
MM37/3
MM55/3
MM75/3
MM110/3 MM150/3 MM220/3 MM300/3 MM400/3 MM550/3
MM750/3
Input voltage range
3 AC 380 V - 500 V +/-10%
Motor output rating a
(kW / hp)
0.37 /
1/
2
0.55 /
3/
4
0.75 / 1
1.1 / 1
1/
2
1.5 / 2
2.2 / 3
3.0 / 4
4.0 / 5
5.5 / 7
1/
2
7.5 / 10
Continuous output
930 VA
1.18 kVA
1.5 kVA
2.1 kVA
2.8 kVA
4.0 kVA
5.2 kVA
7.0 kVA
9.0 kVA
12.0 kVA
Output current (nom.) (400 V / 500 V) a
1.05/0.95A 1.5 / 1.3 A 2.0 / 1.8 A 2.8 / 2.5 A
3.7 / 3.3 A
5.2 / 4.6 A 6.8 / 6.0 A 9.2 / 8.1 A 11.8 / 10.4 A 15.8 / 13.9 A
Output current (max. continuous)
1.2/ 1.06 A 1.6 /1.45 A 2.1 / 1.9 A 3.0 / 2.7 A 4.0 / 3.6 A
5.9 / 5.3 A 7.7 / 6.9 A 10.2 / 9.1A 13.2/ 11.8 A 17.0 / 15.2 A
Input current (
I
rms)
2.2 A
2.8 A
3.7 A
4.9 A
5.9 A
8.8 A
11.1 A
13.6 A
17.1 A
22.1 A
Recommended mains fuse
10 A
16 A
20 A
25 A
Recommended lead
Input
1.0 mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
cross-section (min.)
Output
1.0 mm
2
1.5 mm
2
2.5 mm
2
Dimensions (mm) (w x h x d)
73 x 175 x 141
149 x 184 x 172
185 x 215 x 195
Weight (kg / lb)
0.75 / 1.7
2.4 / 5.3
4.8 / 10.5
Integrated Class A filters are also available (see below).