5. SYSTEM PARAMETERS
English
Parameter Function
Range
[Default]
Description / Notes
© Siemens plc 1999
G85139-H1750-U049-C1
29
19/08/99
P033
•
Jog Ramp-up time (seconds)
0 - 650.0
[10.0]
This is the time taken to accelerate from 0 Hz to maximum frequency
(P013) for jog functions. It is
not
the time taken to accelerate from 0
Hz to the jog frequency.
If one of the digital inputs is programmed to select jog ramp times (e.g.
P051-53=16), the corresponding digital input can be used to select the
ramp time set by this parameter instead of the normal Ramp-up time
set by P002.
P034
•
Jog Ramp-down time (seconds)
0 - 650.0
[10.0]
This is the time taken to decelerate from maximum frequency (P013) to
0 Hz for jog functions. It is
not
the time taken to decelerate from the jog
frequency to 0 Hz.
If one of the digital inputs is programmed to select jog ramp times (e.g.
P051-53, the corresponding digital input can be used to select the
ramp time set by this parameter, instead of the normal Ramp-down
time set by P003.
P041
•
Fixed frequency 1 (Hz)
0 - 400.00
[5.00]
Valid if P006 = 2 and P053 = 6 or 18, or P053-55=17
P042
•
Fixed frequency 2 (Hz)
0 - 400.00
[10.00]
Valid if P006 = 2 and P052 = 6 or 18, or P053-55=17
P043
•
Fixed frequency 3 (Hz)
0 - 400.00
[15.00]
Valid if P006 = 2 and P051 = 6 or 18, or P053-55=17
P044
•
Fixed frequency 4 (Hz)
0 - 400.00
[20.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P045
Inversion fixed setpoints for
fixed frequencies 1 - 4
0 - 7
[0]
Sets the direction of rotation for the fixed frequency:
FF 1
FF 2
FF 3
FF4
P045 = 0
⇒
⇒
⇒
⇒
P045 = 1
⇐
⇒
⇒
⇒
P045 = 2
⇒
⇐
⇒
⇒
P045 = 3
⇒
⇒
⇐
⇒
P045 = 4
⇒
⇒
⇒
⇐
P045 = 5
⇐
⇐
⇒
⇒
P045 = 6
⇐
⇐
⇐
⇒
P045 = 7
⇐
⇐
⇐
⇐
⇒
Fixed setpoints not inverted.
⇐
Fixed setpoints inverted.
P046
•
Fixed frequency 5 (Hz)
0 - 400.00
[25.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17
P047
•
Fixed frequency 6 (Hz)
0 - 400.00
[30.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P048
•
Fixed frequency 7(Hz)
0 - 400.00
[35.00]
Valid if P006 = 2 and P051 = P052 = P053 = 17.
P050
Inversion fixed setpoints for
fixed frequencies 5 - 7
0 - 7
[0]
Sets the direction of rotation for the fixed frequency:
FF 5
FF 6
FF 7
P050 = 0
⇒
⇒
⇒
P050 = 1
⇐
⇒
⇒
P050 = 2
⇒
⇐
⇒
P050 = 3
⇒
⇒
⇐
P050 = 4
⇒
⇒
⇒
P050 = 5
⇐
⇐
⇒
P050 = 6 or 7
⇐
⇐
⇐
⇒
Fixed setpoints not inverted.
⇐
Fixed setpoints inverted.