Technical data
8
Electrical data
Supply voltage
24 V AC
24 V DC
Permitted range
-15% +10%
-15% +20%
Current consumption from power supply
max. 25 mA
Current consumption via BUS
5 mA
Data transmission rate EIB
9600 baud
Design and construction
Standard width
2 WM
Dimensions (W x H x D)
36 x 90 x 55 mm
Weight
Approx. 50 g
Mounting options
35 mm DIN rail
Wall mounting
Operating state indicators
RUN/STOP LED for LOGO!
BUS LED for EIB/KNX
Control elements
EIB/KNX programming key S1
Connections
LOGO! interfacing
Standard expansion interface
for LOGO! 12/24 V a. 115/240 V
EIB interfacing (TP 256)
max. torque
2-pole screw terminal (0.5 – 2.5 mm²); 0.5 Nm
Power supply
max. torque
2-pole screw terminal (0.5 – 2.5 mm²); 0.5 Nm
Standard bus cable to be used
YCYM or J-Y(ST)Y (2 x 2 x 0.8 mm²)
Virtual digital inputs (I)
max. 16
Virtual digital outputs (Q)
max. 12
Virtual analog inputs (AI)
max. 8
Virtual analog outputs (AO)
max. 8
Max. number of group addresses
64
Max. number of associations
64
Summary of Contents for Logo! CM EIB
Page 1: ...Communication with LOGO on the EIB according to the Konnex standard Manual Edition 03 2010 ...
Page 2: ......
Page 12: ...Application planning 2 3 Storage CM EIB 12 Manual 03 2010 J31069 D1262 U002 A4 7618 ...
Page 14: ...Installation 3 1 Installation CM EIB 14 Manual 03 2010 J31069 D1262 U002 A4 7618 ...
Page 18: ...Connecting 4 2 Connecting the EIB CM EIB 18 Manual 03 2010 J31069 D1262 U002 A4 7618 ...
Page 24: ...Service and maintenance 6 3 Disposal CM EIB 24 Manual 03 2010 J31069 D1262 U002 A4 7618 ...
Page 42: ...Functions 7 4 EIB communication CM EIB 42 Manual 03 2010 J31069 D1262 U002 A4 7618 ...