Commissioning
5.3 Response to communications failure
CM EIB
Manual, 03/2010, J31069-D1262-U002-A4-7618
21
5.3
Response to communications failure
LOGO! power failure
In the event of LOGO! power failure or interruption of communication to the LOGO! master or
the left communication partner, the outputs are set to 0. The RUN/STOP LED glows red after
one second.
Power restoration to LOGO!
LOGO! restarts, CM sends the parameterized states.
CM power failure
All inputs of the LOGO! master on the EIB are set to 0 by the LOGO! master.
Power restoration to CM
All inputs of the LOGO! master on the EIB are updated. Depending on the parameterization,
the inputs are read by the EIB.
Short-circuit or interruption of BUS
The last value received at inputs and outputs is retained until a new value is received. After 5
seconds, the red LED lights up.
BUS restored
When the BUS returns, the CM behaves neutrally, i.e. it does not send any message frames.