Parameterization example
The output of a LOGO! has to be switched on every year
on March 1 and switched off on April 4, switched on again
on July 7 and switched off on November 19. For this you
require 2 twelve-month time switches each of which is con-
figured for one of the on periods. The outputs are then
linked by an OR block.
B01:No
MM.DD
On=03.01
Off=04.04
B02:No
MM.DD
On=07.07
Off=11.19
On
Off
1 March
4 April
7 July
19 November
B01
B02
LOGO! Functions