![Siemens LOGO! 24 Manual Download Page 207](http://html.mh-extra.com/html/siemens/logo-24/logo-24_manual_377210207.webp)
199
LOGO! Manual
A5E00067781 01
A.5 Technical Specifications: LOGO! 12...
LOGO! 12RCL
LOGO! 12/24RC
LOGO! 12/24RCo
Power supply
Input voltage
12 V DC
12/24 V DC
Permissible range
10.8 ... 15.6 V DC
10.8 ... 15.6 V DC
20.4 ... 28.8 V DC
Power consumption
10 ... 165 mA
(from 12 V DC)
10 ... 120 mA
(from 12/24 V DC)
Voltage failure bridging
Typically 5 ms
Typically 5 ms
Power loss
0.1 ... 2.0 W
(at 12 V DC)
0.1 ... 1.2 W
(at 12/24 V DC)
Clock buffering at 25
C
Typically 80 h
Typically 80 h
Accuracy of the real–time
clock
Max.
5 s a day
Max.
5 s a day
Electrical isolation
No
No
Reverse polarity protection
Yes
Yes
Digital inputs
Number
12
8
Electrical isolation
No
No
Input voltage L+
Signal 0
< 4 V DC
< 5 V DC
g
Signal 1
> 8 V DC
> 8 V DC
Input current at
Signal 0
< 0.5 mA
> 1.5 mA
< 1.0 mA (I1...I6)
< 0,05 mA (I7, I8)
Signal 1
> 1.5 mA
,
( ,
)
> 1.5 mA (I1...I6)
> 0,1 mA (I7, I8)
Delay time at
0 after 1
Typically 1.5 ms
Typically 1.5 ms
1 after 0
y
y
Typically 1.5 ms
y
y
Typically 1.5 ms
Technical Specifications
Summary of Contents for LOGO! 24
Page 216: ......