115
LOGO! Manual
A5E00067781 01
4.4.17
Analog Trigger
Brief description
The output is switched on, if the analog value exceeds a
parameterizable on threshold. The output is switched off if
the analog value falls below the parameterizable off thresh-
old (hysteresis).
Symbol in
LOGO!
Connection
Description
Input Ax
At the output Ax, apply the
analog signal to be evalu-
ated.
Use the connectors I7 (AI1)
or I8 (AI2).
0-10 V corresponds to
0-1000 (internal value).
Parameter Par:
,
, SW
,
SW
: Gain in %
Value range 0..1000 %
: Offset
Value range
999
SW
: on threshold
Value range
19990
SW
: off threshold
Value range
19990
Output Q
Q is set or reset depending
on the threshold values.
Gain and Offset parameters
Refer to the information in Section 4.3.6 on the Gain and
Offset parameters.
LOGO! Functions
Summary of Contents for LOGO! 24
Page 216: ......