Application guidelines 

en

IS390:

  

 

Volumetric detection, range 21 m. 

IS390H:

 Effective volumetric detection,  

range 27 m.

 

 

Installation 

Coverage zone 

(Fig. 1) 

 

The detector reacts to fast and slow 

movements of an intruder within the specified 

environmental conditions. The detection 

capacity is, however, reduced where there is 

only a slight temperature difference between 

the intruder and environment or where weather 

conditions are extreme. 

 The reaction of the detector is most sensitive to 

movements which are transverse to the 

coverage zone. 

 The coverage zone is limited by walls and 

other objects. The following points shall be 

noted to obtain optimum sensitivity and reduce 

false alarms. 

Align the coverage zone so that it is bounded 

at the end by a reference which is as uniform 

as possible (floor, wall).  

Align the detector so that a potential intruder 

has to pass through the complete coverage 

zone. 

There should be no large objects within the 

coverage zone, which, for instance, could 

move considerably due to wind gusts (large 

branches, bushes, high grass). 

The inadvertent intrusion of people and 

animals must be prevented, e.g. by a fence. 

 For installations where the range of a detector 

is not sufficient, subdivide the area to be 

monitored into sections covered by several 

detectors.   

 

Note that the masking of the 

coverage zone is not monitored. 

 

Mounting 

(Fig.2) 

The detector is to be mounted 2.5 m to 4.0 m 

above the ground 

either by screwing to a stable surface 

  or 

strapping to a stable pole. 

 

The cable inlets must not be changed. 

Do not seal the cable inlets because 

otherwise condensation can form 

within the detector. 

If the cable diameter is too small, 

reinforce the cable using insulating 

tape. 

Alignment of detector 

The detection range of a PIR detector is not 

limited but a function of size, speed and 

temperature contrast of a target against its 

background. The detector should be aligned so 

that a natural or artificial background at the end 

of the range terminates the field of view. 

For details refer to fig. 3 

 

The monitored area must then be 

checked by a walk test. Refer to 

”Walk test” section.  

 

Wiring

 (Fig. 5) 

The diagram shows the terminal block 

connections. 

 

Programming 

Sensitivity 

The various settings of the IS390 are made by 

means of multiple DIP

Switches on the printed 

circuit board. 

DIP1

DIP2 Sensitivity 

IS390 

IS390H 

DIP 1 

DIP 2 

40% 40%  OFF OFF 
75 % 

75 % 

OFF 

ON 

Max. Max.  ON  OFF 
Software Software  ON 

ON 

 

The 

DIP–Switches 1 and 2

 are for sensitivity 

setting depending on the 

required detection 

range

. If the maximum required range is less 

than the nominal range of the detector, it is 

recommended to reduce the range setting to 

reduce nuisance alarms. 

 
 
Adaptive threshold decoding (ATD) 

The background noise is constantly averaged 

and used to adjust the threshold levels for the 

alarm. This special feature is reducing the 

probability of nuisance alarms caused by wind, 

moving vegetation or objects that have a thermal 

contrast although usually weaker than a person. 

DIP3 Adaptive Threshold Decoding 
ATD OFF 

OFF 

ATD ON 

ON 

 

 

DIP4 Pulse counter 
Pulse counter OFF 

OFF 

Pulse counter ON 

ON 

 

 

IS390H 

Unlike the IS390, the H version offers a 25% 

greater effective region, an optimised infrared 

filter through the silicon window and controlled 

heating which prevents the lenses from fogging 

up or freezing. 

 

 

Walk test 

Doing walk test using the ISWT41, in HW mode 

the DIP

Switch 5 needs to be set to ’on’. After 

the walk test, the ’test’ mode needs to be 

switched ’off’. 

DIP5 Walk Test 
Test OFF 

OFF 

Test ON 

ON 

Important: The transmitter ISWT41

T of the 

cordless installation tester has to be placed 

within the housing with the detector cover closed 

and securely tightened. The antenna of the 

transmitter needs to be placed straight in the 

detector housing. 

 

 

Anti Vandal Function 

The IS390/IS390H is equipped with a 

sophisticated protection against vandalism. 

These detectors can sense certain changes of 

their alignment from the original position as set 

during the installation. A change of the detectors 

alignment generates a permanent alarm until the 

detectors alignment is back in its original position 

or until the position has purposely been reset.  

After the turn

on time of typ. 60 seconds from 

power on, the detector determines and stores its 

alignment position (only with detector cover 

closed). 

After opening and closing the cover with the unit 

powered on, the detector determines its 

alignment position and stores the position value 

after 5 minutes again without having the detector 

in permanent alarm state. 

The anti vandal sensor can be reset with a 

power off

on (60 seconds). 

DIP6 Anti Vandal Function 
Anti Vandal OFF 

OFF 

Anti Vandal ON 

ON 

 

Hardware Mode: 

When operating the detector in the HW mode, 

the anti vandal function is activated by setting 

’DIP’ switch 6 to ’ON’ 

 

 

 
 

Maintenance 

Check the detector regularly (at least twice a 

year) for correct functioning (walk test), 

cleanliness and security of attachment. 

Clean the detector window only with a soft 

cloth. Do not use solvents. 

Check the inside of the detector for humidity 

and correct sealing of the cover. 

After extreme weather conditions (storm, 

snowstorm, hail etc.), check the detector for 

damage. Remove snow or dust from the 

detector window. 

 

 

Accessories 

Interface Module ISIF485B and Installation 

Software  

The Installation Software is very useful for 

alignment and signal check during setting up and 

routine maintenance. It will indicate the 

amplitudes generated by wanted as well as 

unwanted targets and help setting the sensitivity 

control correctly during walk tests and also show 

the magnitude of disturbance signals. The 

installation software is to be installed on a PC; 

an interface module is required to convert 

RS232/USB to RS485. The information for 

installation and signal monitoring is displayed on 

the screen of the PC. If more than one detector 

is connected to the same RS485 communication 

bus, each detector needs to have a different 

address (ID) The RS485 standard requires a bus 

topology. To ensure proper communication, the 

dataline must be terminated on both ends. The 

ISIF485B features a built

in termination resistor.  

The input cable is 5.0m long and is terminated 

with a RJ12 connector fitting into the test socket 

on the electronic board of the detector. 

 

 

Technical data 

Supply 

Supply voltage ...............10,5...30,0 VDC/24 VAC 

Power consumption (at 12 VDC): 

 quiescent current IS390 / IS390H........... 18 mA 

 Heating power ..................... typ. 2 W at 

40 °C 

Alarm outputs 

Relay ...............................................pen on alarm 

 alarm holding time ...................................>2.5 s 

 contact load  ................. 28 VDC/250 mA, 10 W 

Electronic output, terminal 4 ..............alarm 

0 V 

open collector 

Tamper contact 

 contact load .............................30 VDC/100 mA 

 

Environmental conditions 

 operating temperature 

IS390 .........................................

20 °C ... +60 °C 

IS390H ......................................

40 °C ... +60 °C 

 air humidity EN60721 .<95 %rF, not co densing 

 housing protection 

class EN60529, EN50102............................. IP64 

 

Order information 

IS390 PIR detector ...................BPZ:5398270001 

IS390H PIR detector......................A5Q00005094 

ISIF485B Installation module 

and SW ..........................................A5Q00026219 

ISMD41

3 Pole Mount Hardware ..A5Q00026220 

ISWT41 Cordless Walktester.........A5Q00026218 

 

 

 

 

Summary of Contents for Intrunet IS390

Page 1: ...é de façon que les jambes d une personne situé à l extrémité de la zone sensible de détection déclenchent une alarme Allineamento verticale tipico per l area di copertura definita per dettagli vedere fig 1 Il rivelatore deve essere orientato in modo tale che all estremità del campo sotto controllo venga rivelata almeno la metà inferiore di una persona ritta in piedi Alineación vertical típica para...

Page 2: ...en réalisant des tests de déplacement it Orientamento del rivelatore L allineamento verticale può considerarsi ottimale quando il limite superiore più distante del volume sorvegliato è posizionato tra 1 5m sopra il punto di terra posto al margine dell area di copertura richiesta premesso che il campo visivo sia determinato ovvero non si perda all infinito L allineamento di massima può essere esegu...

Page 3: ...010070_b_ _ p3 ...

Page 4: ...itch 5 needs to be set to on After the walk test the test mode needs to be switched off DIP5 Walk Test Test OFF OFF Test ON ON Important The transmitter ISWT41 T of the cordless installation tester has to be placed within the housing with the detector cover closed and securely tightened The antenna of the transmitter needs to be placed straight in the detector housing Anti Vandal Function The IS39...

Page 5: ...zung die ein Beschlagen oder Gefrieren der Optik verhindert Gehtest Für den Gehtest mit dem ISWT41 muss der DIP Schalter 5 im HW Modus auf ON gestellt werden Nach dem Gehtest muss der Modus Test auf OFF gestellt werden DIP5 Gehtest Test AUS OFF Test EIN ON Wichtig Der Sender ISWT41 T des schnurlosen Installationstesters muss innerhalb des Gehäuses platziert werden Dabei muss die Abdeckung des Meld...

Page 6: ...re le test de marche avec l ISWT41 en mode matériel le commutateur DIP 5 doit être réglé sur ON Après le test de marche le mode test doit être remis sur OFF DIP5 Test de marche Test DESACTIVE OFF Test ACTIVE ON Important L émetteur ISWT41 du testeur sans fil doit être placé à l intérieur du boîtier avec le couvercle de détecteur fermé et correctement verrouillé L antenne de l émetteur doit être pl...

Page 7: ... deve essere impostato su ON Completato il test di attraversamento è necessario disattivare OFF la modalità di test DIP5 Test di attraversamento Test DISATTIVATO OFF Test ATTIVATO ON Importante Il trasmettitore ISWT41 T del dispositivo cordless per test di installazione si deve posizionare nell alloggiamento con il coperchio del rivelatore chiuso e ben stretto L antenna del trasmettitore va posizi...

Page 8: ...ortante El transmisor ISWT41 T del comprobador inalámbrico de la instalación debe situarse dentro de la carcasa con la cubierta del detector cerrada y firmemente apretada La antena del transmisor debe colocarse de forma recta en la carcasa del detector Función antivandálica El IS390 IS390H está equipado con una sofisticada protección contra el vandalismo Estos detectores pueden detectar ciertos ca...

Page 9: ... DIP schakelaar 5 in hardwaremodus op AAN worden gezet Na de looptest moet de test modus op UIT worden geschakeld DIP5 Looptest Test UIT OFF Test AAN ON Belangrijk De zender ISWT41 T van het draadloze installatietestapparaat moet binnen de behuizing worden geplaatst met gesloten en goed vastzittende detectorkap De antenne van de zender moet recht in de behuizing van de detector worden geplaatst An...

Reviews: