5. Make sure that the holder (3) latches into place correctly.
a
When the battery connector is connected, the internal alarm indicator lights
up red for 5 seconds.
a
After a further 10 seconds, the radio fire detector signals that it is not
installed on the detector base and the internal alarm indicator flashes. If it
flashes red, this indicates the factory settings. If it flashes green, this
indicates that the radio fire detector has already been logged on to a radio
gateway.
a
If this does not happen, this means the battery pack is defective and must
not be used.
6. Insert the radio fire detector into the detector base.
a
The internal alarm indicator flashes green and the radio fire detector is
logged on to the radio gateway.
a
If the process of logging on to the radio gateway is successful, the internal
alarm indicator stops flashing.
a
The radio fire detector is now installed and is ready for commissioning.
See also
2
Internal alarm indicator [➙ 19]
Mounting / Installation
Mounting radio fire detector FDOOT271-O
5
34 | 50