3.3.5 Renovation mode
Renovation mode is set using the control panel.
Renovation mode can be used under the following conditions:
●
If there is a large amount of dust in the air around the radio fire detector
temporarily
●
If there are aerosols in the air around the radio fire detector temporarily
The radio fire detector does not issue alarms in renovation mode until a
temperature of 80 °C has been exceeded for 20 seconds.
You will find more detailed information in the fire detection system documentation.
3.3.6 Test mode
In test mode the radio fire detectors react faster and with a higher sensitivity level.
For testing purposes, the radio fire detectors can be set to test mode using the
control panel or the FXS2061-O Wireless-Diagnose-Tool.
The following tests can be performed:
●
Test of optical detector function using test gas
●
Test of heat detector function using hot air
You will find more detailed information in the fire detection system documentation.
3.3.7 Interface to service devices
The fire control panel or the FXS2061-O Wireless-Diagnose-Tool software is used
to read out and set the parameter sets.
Structure and function
Function
3
22 | 50
A6V10425624_en--_h
Summary of Contents for FDOOT271-O
Page 49: ...A6V10425624_en _h 49 50 ...