4.2 Parameter sets for FDOOT271-O
4.2.1 Sensor mode 0 'Neural fire detector'
4.2.1.1 Description
(Parameter set numbers in brackets)
Robust (0)/(2):
The priority of the 'Robust' parameter set is to a robust response. It is thus
particularly suited to application in rooms where deceptive phenomena such as
cigarette smoke or dust can be expected. The 'Robust (2)' parameter set is suitable
for higher rooms.
Suppression (5):
Thanks to its very robust behavior, the 'Suppression' parameter set is particularly
suitable for rooms where deceptive phenomena such as cigarette smoke or
exhaust fumes can be expected. It reacts in a very robust way to the deceptive
phenomenon vapor.
Fast Response (6):
This parameter set reacts in a fast and highly sensitive manner. It is thus especially
suited for rooms without deceptive phenomena, where the priority is on detecting
the fire as early as possible.
4.2.1.2 Use
No.
Name
Risk of damage to
persons
Concentration of
valuable items
Room
geometry
Deceptive
phenomena
Risk of fire
Critical fire size
small…
large
low…
high
simple…
complex
few…
many
small…
large
small…
medium
0
Robust
2
Robust
5
Suppression
6
Fast Response