background image

About this document
Applicable documents

1

6 | 50
Building Technologies

007023_k_en_--

Fire Safety

2017-11-22

Target groups

The information in this document is intended for the following target groups:

Target group

Activity

Qualification

Product Manager

Is responsible for information

passing between the manufacturer

and regional company.
Coordinates the flow of information

between the individual groups of

people involved in a project.

Has obtained suitable specialist

training for the function and for the

products.
Has attended the training courses

for Product Managers.

Project Manager

Coordinates the deployment of all

persons and resources involved in

the project according to schedule.
Provides the information required to

run the project.

Has obtained suitable specialist

training for the function and for the

products.
Has attended the training courses

for Project Managers.

Installation personnel

Assembles and installs the product

components at the place of

installation.
Carries out a performance check

following installation.

Has received specialist training in

the area of building installation

technology or electrical installations.

Commissioning personnel

Configure the product at the place

of installation according to

customer-specific requirements.
Check the product operability and

release the product for use by the

operator.
Searches for and corrects

malfunctions.

Has obtained suitable specialist

training for the function and for the

products.
Has attended the training courses

for commissioning personnel.

Maintenance personnel

Carries out all maintenance work.
Checks that the products are in

perfect working order.
Searches for and corrects

malfunctions.

Has obtained suitable specialist

training for the function and for the

products.

Source language and reference document

The source/original language of this document is German (de).
The reference version of this document is the international version in English.

The international version is not localized.

Document identification

The document ID is structured as follows:

ID code

Examples

ID_ModificationIndex_Language_COUNTRY
-- = multilingual or international

A6V10215123_a_de_DE
A6V10215123_a_en_--
A6V10315123_a_--_--

Date format

The date format in the document corresponds to the recommendation of

international standard ISO 8601 (format YYYY-MM-DD).

Summary of Contents for FDCI222

Page 1: ...FDCI222 FDCIO222 FDCIO224 Input module input output module Technical Manual 007023_k_en_ Building Technologies 2017 11 22 Control Products and Systems ...

Page 2: ...communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechn...

Page 3: ...up 17 3 2 1 Input module FDCI222 18 3 2 2 Input output modules FDCIO222 and FDCIO224 19 3 2 3 Printed circuit board view 20 3 2 4 LEDs 21 3 3 Function 22 3 3 1 Block diagram 22 3 3 2 Inputs 23 3 3 2 1 Configuration options 23 3 3 2 2 Circuit 24 3 3 3 Outputs only with FDCIO222 FDCIO224 25 3 3 4 Monitoring the control with the inputs only with FDCIO222 FDCIO224 26 3 3 5 Line separator 27 3 3 6 Diag...

Page 4: ...figuration sheet 36 4 6 Environmental influences 36 5 Mounting Installation 37 5 1 Mounting on a U rail 37 5 2 Mounting in housing FDCH221 38 5 3 Connecting the module 39 6 Commissioning 40 7 Maintenance Troubleshooting 41 7 1 Performance check 41 7 2 Test mode 41 7 3 Localization mode 41 7 4 Status retrieval 41 8 Specifications 42 8 1 Technical data 42 8 2 Dimensions 45 8 3 Environmental compatib...

Page 5: ...purpose This document contains all information on the input module FDCI222 and the input output modules FDCIO222 and FDCIO224 Following the instructions consistently will ensure that the product can be used safely and without any problems Scope The document is valid for the following modules Input module FDCI222 Input output module FDCIO222 Input output module FDCIO224 Intended use The input modul...

Page 6: ...st training in the area of building installation technology or electrical installations Commissioning personnel Configure the product at the place of installation according to customer specific requirements Check the product operability and release the product for use by the operator Searches for and corrects malfunctions Has obtained suitable specialist training for the function and for the produ...

Page 7: ...ication between steps in a sequence e g Menu bar Help Help topics Text Identification of a glossary entry Supplementary information and tips The i symbol identifies supplementary information and tips for an easier way of working 1 1 Applicable documents Document ID Name 007024 Data sheet Input module FDCI222 Input output modules FDCIO222 FDCIO224 007227 Technical manual Detector exchanger and test...

Page 8: ...the document ID in the Find by keyword input box You will also find information about search variants and links to mobile applications apps for various systems on the home page 1 3 Technical terms Term Explanation ABS Acrylonitrile butadiene styrene plastic ASA Acrylic ester styrene acrylnitrile plastic ES Product version FS20 FS720 Addressed detector line LED Light emitting diode MC link Maintena...

Page 9: ...uments chapter Download center chapter updated Changes in the Technical data chapter Portfolio FC360 added Editorial revision and adaptation of entire document i 12 2009 Maximum current quiescent current connection factor changed Housing FDCH29x replaced with FDCH221 Editorial changes made h 09 2007 Diagnosis levels changed Output configuration changed Images with language texts replaced by langua...

Page 10: ...dangers the type of danger or possible consequences measures and prohibitions examples of which are shown in the following table General danger Explosive atmosphere Voltage electric shock Laser light Battery Heat Signal word The signal word classifies the danger as defined in the following table Signal word Danger level DANGER DANGER identifies a dangerous situation which will result directly in d...

Page 11: ...is shown as follows WARNING Nature and origin of the danger Consequences if the danger occurs Measures prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows NOTICE Nature and origin of the danger Consequences if the danger occurs Measures prohibitions for danger avoidance ...

Page 12: ...nce and supervision of a qualified electrician in accordance with the electrotechnical regulations Wherever possible disconnect products from the power supply when carrying out commissioning maintenance or repair work on them Lock volt free areas to prevent them being switched back on again by mistake Label the connection terminals with external voltage using a DANGER External voltage sign Route m...

Page 13: ...y be produced Before testing the remote transmission inform the corresponding alarm and fault signal receiving stations Modifications to the system design and the products Modifications to the system and to individual products may lead to faults malfunctioning and safety risks Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions Modu...

Page 14: ...jury and damage to property in the event of a fire Read the Release Notes before you plan and or configure a fire detection installation Read the Release Notes before you carry out a firmware update to a fire detection installation NOTICE Incorrect planning and or configuration Important standards and specifications are not satisfied Fire detection installation is not accepted for commissioning Ad...

Page 15: ... outputs can be operated independently However it is also possible to monitor the control of an output by means of an input A control function can be performed on the output e g Close door for example The correct execution of the control can be monitored on the input e g door is closed The difference between FDCIO222 and FDCIO224 is in the circuitry for the monitoring of the inputs FDCIO224 meets ...

Page 16: ... FDCIO222 A5Q00002369 Input output module FDCIO224 A5Q00018689 Input output module Scope of delivery Type Scope of delivery FDCI222 Input module FDCI222 4x 3 01 k resistor 4x 1 15 k resistor 2x mounting foot FDCIO222 Input output module FDCIO222 4x 3 01 k resistor 4x 1 15 k resistor 2x mounting foot FDCIO224 Input output module FDCIO224 4x 2 7 k resistor 4x 560 resistor 2x mounting foot ...

Page 17: ...the product version can be found after the device order number Figure 2 Example of a product label with details of the product version Depending on the product and various approvals the product labels may differ in terms of the information type and layout Look for your device s order number on the product label You will find the product version after the order number 3 2 Setup The modules consist ...

Page 18: ... 007023_k_en_ Fire Safety 2017 11 22 3 2 1 Input module FDCI222 Figure 3 Overview FDCI222 1 Cable tie holder 4 Connection for MC Link 2 Holes for securing the module 5 Terminal inputs 3 Terminal FDnet C NET 6 Holes for mounting feet FDCM291 6 1 1 2 1 1 3 4 2 5 ...

Page 19: ...22 3 2 2 Input output modules FDCIO222 and FDCIO224 Figure 4 Overview of FDCIO222 and FDCIO224 1 Cable tie holder 5 Connection for MC Link 2 Terminal outputs 6 Terminal inputs 3 Holes for securing the module 7 Holes for mounting feet FDCM291 4 Terminal FDnet C NET 7 1 2 1 3 2 1 1 4 5 3 6 ...

Page 20: ...output OUT B only for FDCIO22x 8 LED for indicating the status of output OUT A only for FDCIO22x 9 LED for indicating the status of input IN 4 10 LED for indicating the status of input IN 3 11 LED for indicating the status of input IN 2 12 LED for indicating the status of input IN 1 13 LED indicator for fault 14 LED indicator for operation 15 Terminals for LINE FDnet C NET detector line 16 Termina...

Page 21: ...rmal operation Green LED flashes every 1 sec Localization mode Yellow LED is flashing Fault Yellow and green LEDs are flashing Test mode LEDs for inputs and outputs For each input and each output there is an LED Status LED Meaning Red LED is flashing Input activated Orange LED is flashing Command for the activation of the output received by the control unit The displays can be deactivated if neces...

Page 22: ... The communication with the control panel is performed via the FDnet C NET detector line Configuration is performed on the control panel The modules are normally in operating mode For service purposes the modules can be switched to test mode The modules require no auxiliary power supply µP IN 1 IN 2 IN 3 IN 4 OUT D OUT C OUT A OUT B OUT C OUT D OUT B OUT A IN 1 IN 2 IN 3 IN 4 OC A OC B OC C OC D I...

Page 23: ...itoring and circuitry The input lines are monitored for Open line or Open line and short circuit To facilitate this resistors must be connected to the lines of the inputs When a short circuit of an open line occurs on one of the input lines a fault message is transmitted to the control unit The inputs must be potential free Filter time The statuses of the inputs are polled several times a second T...

Page 24: ... FDCI222 FDCIO222 connection diagram applies to monitoring for short circuit and open line When the line is only to be monitored for open line the resistor Rs 1 15 k must not be provided Input output module FDCIO224 With FDCIO224 two different kinds of circuitry are possible Figure 8 FDCIO224 circuitry Connection diagram 1 The 560 monitoring resistor applies to monitoring for short circuit and ope...

Page 25: ...ivated the control remains permanently active Once activated the contact only remains active for a certain time How long the contact remains active can be configured pulse duration Failsafe behavior when the FDnet C NET detector line is current free or in degraded mode e g in case of a failure of the processor in the control panel The error behavior defines the position of the contact in the event...

Page 26: ...pired The delay period can be adjusted Failsafe behavior when the FDnet C NET detector line is current free or in degraded mode e g in case of a failure of the processor in the control panel The error behavior defines the position of the contact in the event of an error The contact remains in the same position as before the error The contact is activated in case of an error The contact is deactiva...

Page 27: ...OUT B IN 3 OUT C IN 4 OUT D 3 3 5 Line separator All FDnet C NET devices are equipped with a line separator The FDnet C NET device is equipped with electronic switches which isolate the defective part in case of a short circuit on the FDnet C NET detector line The rest of the detector line remains serviceable On a loop line all FDnet C NET devices remain fully functional after a single short circu...

Page 28: ... You will find additional information in documents 007227 and 009718 Information displayed on the detector exchanger and tester Meaning Measures No deviation Normal no fault is present Input output module is fully functional none Any fault message 1 Fault present Error with the input circuitry open line short circuit deviation Checking the input circuitry parameter setting resistors short circuit ...

Page 29: ...t the exact location of the detector triggering the alarm When the outputs are used for controls e g fire controls the outputs take on the configured default position in case of a communication failure or current free FDnet C NET only devices with ES 30 Degraded mode operation on the FDnet C NET is not supported in the same way by all control panels The information in the List of compatibility and...

Page 30: ...erminal for connecting cables For T branches of additional cabling e g for cable shielding detector heating units sounder base external alarm indicators etc For conductor cross sections of 0 5 2 5 mm 3 poles Order number BPZ 4942340001 3 4 4 M20 x 1 5 metal cable gland For introducing a cable into a housing For cable diameters of 3 5 5 5 mm Temperature range 40 100 C Allows for increased IP protec...

Page 31: ...r number A5Q00004479 3 4 6 Cable ties 2 4 x 137 For strain relief on the connection wires or generally for attachment Made from polyamide Compatible with Input module FDCI22x CN Input output module FDCIO22x CN FDCL221 line separator Multi line separator module FDCL221 M Radio gateway FDCW221 and FDCW241 Zone module external powered FDCI223 FDCI723 Order number BPZ 1825330001 ...

Page 32: ...fine the type of monitoring and configuration of the inputs 4 Define the configuration of the outputs 5 Fill out the configuration sheet 4 1 Compatibility Compatible with control panels that support the FDnet C NET detector line Detector line FC20xx FC72x SIGMASYS AlgoRex FC360 FDnet X X 1 X 1 C NET X X 1 With suitable line card X compatible not compatible You will find detailed information in the...

Page 33: ...se as possible to the fire control This simplifies the cabling Use the housing FDCH221 for the following installation situations Outside a switch cabinet Outside a control panel In a wet or dirty environment You will find more detailed information in the fire detection system documentation Procedure WARNING Voltages up to AC 250 V on the terminals of the module Danger to life through contact with ...

Page 34: ...e The filter time defines the signal length which is definitely suppressed In order to ensure correct activation or deactivation the input signal must be present for at least as long as the filter time plus 0 25 s without interruption Filter times can be set to suppress interfering pulses The following filter times can be set 0 5 s 20 s 150 s 1 s 45 s 180 s 2 5 s 60 s 210 s 5 s 90 s 240 s 10 s 120...

Page 35: ...nce activated the control is permanently active Once activated the control is only active for a certain time The period for which the control remains active can be configured pulse duration The following settings are possible 1 s 5 s 20 s 2 s 10 s 3 s 15 s 1 Determine the type of monitoring equal or reversed polarity 2 Determine the behavior of the control in case of error e g open line to the con...

Page 36: ...ill out the configuration sheet 3 Hand over copies of the completed configuration sheet to the installer and the service technician See also 2 Configuration sheet 47 4 6 Environmental influences If the devices are used in industrial applications consultation with the project manager is required since plastics do not withstand certain environmental conditions The following factors must be taken int...

Page 37: ...ule function due to dust or humidity The only situation in which the housing FDCH221 should not be used is if the module is installed in a closed electrical cabinet or in a control panel When installing the module on a DIN rail proceed as follows 1 Insert the two mounting feet FDCM291 supplied into the module 2 Press the module s two mounting feet against a U rail TS35 until the mounting feet enga...

Page 38: ...nnection terminal The shielding must not touch any extrinsic ground potentials or metal parts in the housing 6 Install the module in the housing using the M3 x 12 fixing screws supplied 7 Connect the cables to the corresponding terminals 8 Close housing using supplied screws Cable with diameter 1 5 mm If the cable diameters on the inputs outputs are greater than 1 5 mm2 auxiliary terminals must be...

Page 39: ...ve components Use the housing FDCH221 if switching voltages DC 60 V ripple 10 of average value or AC 30 V peak value max 42 4 V on the outputs Ensure that the cables are not supplied with voltage during installation Note the positive and negative poles Only connect one wire per terminal This is the only way to ensure the connection is failure free for the entire service life of the device Connect ...

Page 40: ...ologies 007023_k_en_ Fire Safety 2017 11 22 6 Commissioning The devices are commissioned via the control panel The exact procedure is described in the control panel documentation Conduct a performance check once commissioning is complete ...

Page 41: ... outputs Only the LEDs are activated You will find more detailed information in the fire detection system documentation 7 3 Localization mode For service purposes the modules can be switched to localization mode In this mode the input LED flashes continuously once per second The localization mode does not work with FC20xx FC72x fire control panels 7 4 Status retrieval The modules are equipped with...

Page 42: ...tion factor 1 Separator connector factor 1 Protocol FDnet C NET Compatibility See List of compatibility Line separator Line voltage Nominal DC 32 V Vnom Minimum DC 12 V Vmin Maximum DC 33 V Vmax Voltage at which the line separator opens Minimum DC 7 5 V VSO min Maximum DC 10 5 V VSO max Permanent current when switches are closed Max 1 5 A IC max Switching current e g in the event of a short circui...

Page 43: ...C voltage AC 250 V 4 A 1000 VA DC voltage These values do not apply for inductive or capacitive loads DC 30 V 4 A 120 W Connections Detector line Design Socket strip Cross section 0 2 1 5 mm2 Inputs and outputs Design Socket strip Cross section 0 2 1 5 mm2 MC Link Plug connection 3 5 mm jack socket Ambient conditions Operating temperature 25 60 C Storage temperature 30 65 C Air humidity non conden...

Page 44: ...echanical data Dimensions L x W x H Module 132 x 90 x 21 mm Housing FDCH221 207 x 119 x 50 mm Housing material ABS Color Module carrier RAL 9010 pure white Housing cover Transparent matt Housing FDCH221 RAL 9010 pure white Standards European standards EN 54 17 EN 54 18 CEA GEI I 084 for I O modules ...

Page 45: ... 45 50 Building Technologies 007023_k_en_ Fire Safety 2017 11 22 8 2 Dimensions Input module FDCI222 Input output module FDCIO222 FDCIO224 Housing FDCH221 All dimensions in mm 43 5 118 102 21 A 4 5 46 5 132 8 2 5 8 A A 50 207 119 ...

Page 46: ...ures have been undertaken Use of reusable materials Use of halogen free plastics Electronic parts and synthetic materials can be separated Larger plastic parts are labeled according to ISO 11469 and ISO 1043 The plastics can be separated and recycled on this basis Electronic parts and batteries must not be disposed of with domestic waste Take electronic parts and batteries to local collection poin...

Page 47: ...s Configuration for the inputs Parameters Value IN1 IN2 IN3 IN4 Type of input Danger input Status input Input monitoring Open line monitoring short circuit and open line Input active when contact is Open Closed Filter time Duration ____ s ____ s ____ s ____ s Configuration for the outputs Parameters Value OUT1 OUT2 OUT3 OUT4 Output active when contact is Open NC Closed NO Control monitoring Yes No...

Page 48: ...Environmental compatibility 46 Environmental influences 36 ES Product version 17 EU directives 42 Extinguishing interface 15 F Fault messages 28 Filter time 34 Fire control panel failure Degraded mode operation 29 I Impact Chemicals 36 Moisture 36 Temperature 36 Intelligent detector tester Diagnosis levels 28 Intelligent detector tester FDUD293 MC link 41 Intended use 5 Interface MC link 41 L LED ...

Page 49: ...9 50 Building Technologies 007023_k_en_ Fire Safety 2017 11 22 Standards 44 Status input 23 T Type plate Product version 17 V VdS extinguishing interface Connection 24 FDCIO224 15 Installation specification 33 ...

Page 50: ...onal Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2004 Technical specifications and availability subject to change without notice Document ID 007023_k_en_ Manual FD20 FD720 Edition 2017 11 22 Register 5 ...

Reviews: