Structure and function
Function
3
28 | 50
Building Technologies
007023_k_en_--
Fire Safety
2017-11-22
3.3.6 Diagnosis levels
The devices largely monitor their function autonomously. The following diagnosis
levels are derived from the different control measurements:
Normal
Fault
For details, see table below.
When an error occurs which impairs the correct functionality of the module, a
module fault message is reported. The module contains additional information for
addressing the cause. This can be displayed by the FDUD292 detector exchanger
and tester or FDUD293 intelligent detector tester for example.
You will find additional information in documents 007227 and 009718.
Information displayed on
the detector exchanger
and tester
Meaning
Measures
'No deviation'
Normal, no fault is present
Input/output module is fully functional
none
Any fault message
1
Fault present
Error with the input circuitry (open line,
short-circuit, deviation)
Checking the input circuitry (parameter
setting, resistors, short-circuit, open
line)
Invalid parameter settings
Check the parameter setting
Supply error
Check detector line voltage
Exchange device
Software error (Watchdog error)
Exchange device
Memory error
Exchange device
Communication error between detector
and control panel
Remedy cause
1
This status can be displayed together with other statuses, e.g. 'needed excha.'
(replacement necessary).
See also
2
Applicable documents [ 7]