Specifications
Technical data
8
43 | 50
Building Technologies
007023_k_en_--
Fire Safety
2017-11-22
Inputs
Monitoring voltage
3 V, unloaded
Monitoring resistors
parallel Rp / serial Rs:
FDCI222/FDCIO222
3.01 k / 1.15 k ;
each +/-1 %; 0.25 W
FDCIO224
2.7 k / 560 ; each +/-1 %; 0.25 W
3.3 k / 680 ; each +/-1 %; 0.25 W
Line resistance
Max. 20
Outputs
Max. switching performance at ohmic
load at:
AC voltage
AC 250 V; 4 A; 1000 VA
DC voltage
These values do not apply for
inductive or capacitive loads
DC 30 V; 4 A; 120 W
Connections
Detector line:
Design
Socket strip
Cross-section
0.2…1.5 mm
2
Inputs and outputs:
Design
Socket strip
Cross-section
0.2…1.5 mm
2
MC-Link
Plug connection
3.5 mm jack socket
Ambient conditions
Operating temperature
-25…+60 °C
Storage temperature
-30…+65 °C
Air humidity (non-condensing)
95 % rel.
Protection category (IEC 60529):
Without housing
IP30
With housing FDCH221
IP65
Electromagnetic compatibility:
1 MHz…1 GHz
50 V/m
1 GHz…2 GHz
30 V/m