background image

5

4.0 MAINTENANCE

Fire and Insurance authorities recommend annual inspection and

if necessary, service of fire protection equipment. To insure proper

and reliable operation, we recommend the following inspection and

testing annually by a qualified technician:

1.

The detector head screen should be inspected for dust

accumulations and if excessive, contact your distributor or

factory for service.

2.

Activate a detector. Check that base lamp operates and

that proper fire indications are given by the system. An

ionization detector may be activated by blowing smoke

into the screened chamber or by holding a lighted match

a few inches below it.

3.

Check the supervisory circuit by operating the Reset

Switch to the “reset” position. In this position, the system

should give the required trouble indications.

4.

Check operation of each detector on circuit. Measure

sensitivityof each detector with appropriate sensitivity

checker.

5.0 TROUBLE SHOOTING THE SYSTEM

Perform checks in order following symptom noted. Refer to chart

for proper readings across specific terminals.

A trouble condition may result from any of the following conditions:

• Open circuit detector lines

• Input fuse open*

• Loss of input supply*

• Reset switch not in closed or normal position.

• Alarm silence switch in off normal or silenced position during

non-alarm condition.

*Note items 2 and 3 above.

These conditions cause a change of state of the trouble relay

contacts only and not a visual trouble indication.
Trouble Condition (Trouble contacts in trouble state):

1. Check main power; terminals 1 (+) to 2 (-).
2. Check fuse F1.
3. Check detector circuit voltage: terminals 3 (+) to 4 (-).
Alarm Condition (alarm contacts in alarm state) without symptoms

of fire:

a.

Place Reset Switch in ‘reset’ position and release.

b.

If voltage terminals 3 (+) 4 (-) is less than 20 VDC, check

current terminal 3. If an excess of “Normal” range then check

detector circuit for alarmed detector, correct end of line resistor,

or shorted lines.

VOLTAGE/CURRENT MEASUREMENT CHART

For DC voltage measurement on terminals noted in left hand

column, the positive terminal is listed first.

Terminals

Voltage

Current

Mode

3+ 4-

20-23 VDC

—

Normal

1

2-

42-55 VDC

—

Normal

3

—

14-20 mA DC

Normal

3

—

> 50 mA DC

Alarm

          DETECTORS

May use up to 30 detectors

(selected from any of the

compatible detectors listed at

the right) or may use shorting

devices, detector relays, or

remote lamps (Refer to the

related detector instructions).

 *CP-48 is the compatibility identifier.

    DETECTOR

        BASE

INSTALLATION/

COMPATIBILITY

COMPATIBILITY

      WIRING

   IDENTIFIER

   IDENTIFIER

INSTRUCTIONS

DI-3

         DB-3S

P/N 315-081943-15

DI-4A

          DB-4

P/N 315-085257-11

PE-3

         DB-3S

P/N 315-090875-6

COMPATIBLE DETECTORS*

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for CP-48

Page 1: ... and Smoke Detection and Alarm System Fire Safety Siemens BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Technical Manuals Online http www tech man com firealarmresources com ...

Page 2: ...be returned to manual position before the system will reset 2 2 If Fire Alarm Sounds a Notify the Fire Department If the system is connected to the Fire Department or a central station this is done automatically by the control equipment Keep in mind that the Fire Department or central station should be notified when resetting the system b If fire is not apparent DO NOT RESET SYSTEM Locate the dete...

Page 3: ...ted from a 48 VDC power source having the positive line grounded such as is available in telephone community dial offices The 48 VDC input powers all internal circuitry The DC voltage may vary between the limits of 42 and 55 volts and the limits should not be exceeded The CP 48 Control Unit ungrounded leg must be connected through a separate circuit breaker or fuse directly to the DC power supply ...

Page 4: ... lines to chassis and conduit There should be at least 10 meg resis tance reading between wires and conduit or ground c Connect wires to appropriate terminals of the Model CP 48 For base wiring follow instructions included with base d The manufacturer s service representative will then install detectors and check sensitivity 3 6 Test for System Operation a See that the CP 48 Control Unit is in nor...

Page 5: ... switch in off normal or silenced position during non alarm condition Note items 2 and 3 above These conditions cause a change of state of the trouble relay contacts only and not a visual trouble indication Trouble Condition Trouble contacts in trouble state 1 Check main power terminals 1 to 2 2 Check fuse F1 3 Check detector circuit voltage terminals 3 to 4 Alarm Condition alarm contacts in alarm...

Page 6: ...ESISTOR VALUES ARE IN O s OHMS 1 4W 2 UNLESS OTHERWISE SPECIFIED ALL CAPACITOR VALUES ARE IN µFD MICROFARADS 3 DIODES CR5 CR9 ARE IN4003 4 KT 2 SHOWN ENERGIZED KA 4 SHOWN DE ENERGIZED CP 48 Schematic Technical Manuals Online http www tech man com firealarmresources com ...

Page 7: ...s BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Technical Manuals Online http www tech man com firealarmresources com ...

Reviews: