background image

4

The wire interconnecting the detector bases is continuously super-

vised by a small electrical current flow through the circuit to the end-

of-line resistor (1.8K ohms) mounted in the base of the last detector.

In order to keep this supervision complete, no parallel branching of

wires is permissible. Every base, except the last one, will have one

set of incoming, and one set of outgoing wires.

b. Installing Bases:

Mount end-of-line resistor between appropriate terminals of last base

on circuit, as indicated on wiring diagram. Mount all bases to outlet

boxes. Manual Stations, Thermal Detectors, Air Duct Detectors, etc.,

are to be connected to the circuit at this time. Please refer to wiring

diagrams for specific equipment for connection details.

3.5 Test of Wiring:

Note: 

It is suggested that electrical tests be conducted jointly by the

installer and the manufacturer’s technician or representative. Fifteen

(15) days prior written notice is requested so that the services of the

technician may be scheduled.

The installation of the wiring should be checked as follows:
a.

Detectors should not be in their bases. Temporary jumpers

should be inserted appropriately in all bases. Install end-of-line

resistor to appropriate terminals of last detector on circuit.

Wiring from bases should NOT be connected to Control Panel

at this time.

b.

Check the wiring of the detector circuit with ohmmeter. Resis-

tance reading between wires normally connected to terminals 3

and 4 of the Control Panel should be approximately 1.8K ohms.

Short the detector lines together and megger the combined lines

to chassis and conduit. There should be at least 10 meg resis-

tance reading between wires and conduit or ground.

c.

Connect wires to appropriate terminals of the Model CP-48. For

base wiring, follow instructions included with base.

d.  

The manufacturer’s service representative will then install

detectors and check sensitivity.

3.6 Test for System Operation:

a.

See that the CP-48 Control Unit is in normal standby operation.

b.

To test for supervision of initiating circuit, remove the detector

connected to the last device and check that proper trouble

indicators respond in the system. Re-connect detector.

c.

To test operation of initiating circuit, actuate a detector. Check

that system fire indicators and alarm relay contacts respond to

the alarm.

d.

Test operation of detector circuit, activate each detector and

manual station, one at a time, resetting each, and check that

detector base lamp and the control unit alarm controls operate.

Each ionization detector may be activated by blowing smoke

into the chamber or holding a lighted match a few inches below

it. The manual station on front panel should be checked

independently.

INPUT

48V +7/-6 VDC,

500mA FUSE

INTERNALLY AT 2A

SUPERVISORY 12mA

ALARM 100mA MAX

SUPERVISED

DETECTOR LINES

21.5 VDC

ION OR PHOTO

DETECTOR

THERMAL DETECTOR

MANUAL STATION

TROUBLE

OPERATED

CONTACTS

RATED 1A

120 VAC/48 VDC

ALARM

OPERATED

CONTACTS

RATED 3A

120 VAC/48 VDC

1.8K, 1/2W, 5%

END OF LINE RESISTOR

NOTES

:

1. Contacts are shown in normal supervisory

condition.

2. See wiring diagram of specific detector type

for proper screw terminal connections. Compat-

ible detectors are shown in the Table on page 5.

3. Input voltage not to exceed 56 volts peak.

Figure 3

Wiring Diagram

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for CP-48

Page 1: ... and Smoke Detection and Alarm System Fire Safety Siemens BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Technical Manuals Online http www tech man com firealarmresources com ...

Page 2: ...be returned to manual position before the system will reset 2 2 If Fire Alarm Sounds a Notify the Fire Department If the system is connected to the Fire Department or a central station this is done automatically by the control equipment Keep in mind that the Fire Department or central station should be notified when resetting the system b If fire is not apparent DO NOT RESET SYSTEM Locate the dete...

Page 3: ...ted from a 48 VDC power source having the positive line grounded such as is available in telephone community dial offices The 48 VDC input powers all internal circuitry The DC voltage may vary between the limits of 42 and 55 volts and the limits should not be exceeded The CP 48 Control Unit ungrounded leg must be connected through a separate circuit breaker or fuse directly to the DC power supply ...

Page 4: ... lines to chassis and conduit There should be at least 10 meg resis tance reading between wires and conduit or ground c Connect wires to appropriate terminals of the Model CP 48 For base wiring follow instructions included with base d The manufacturer s service representative will then install detectors and check sensitivity 3 6 Test for System Operation a See that the CP 48 Control Unit is in nor...

Page 5: ... switch in off normal or silenced position during non alarm condition Note items 2 and 3 above These conditions cause a change of state of the trouble relay contacts only and not a visual trouble indication Trouble Condition Trouble contacts in trouble state 1 Check main power terminals 1 to 2 2 Check fuse F1 3 Check detector circuit voltage terminals 3 to 4 Alarm Condition alarm contacts in alarm...

Page 6: ...ESISTOR VALUES ARE IN O s OHMS 1 4W 2 UNLESS OTHERWISE SPECIFIED ALL CAPACITOR VALUES ARE IN µFD MICROFARADS 3 DIODES CR5 CR9 ARE IN4003 4 KT 2 SHOWN ENERGIZED KA 4 SHOWN DE ENERGIZED CP 48 Schematic Technical Manuals Online http www tech man com firealarmresources com ...

Page 7: ...s BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Technical Manuals Online http www tech man com firealarmresources com ...

Reviews: