background image

3

3.0 INSTALLATION AND WIRING

The reliability of any system depends to a great extent on the proper

installation of the control units, detectors, associated equipment, and

wiring. These instructions outline the requirements for a satisfactory

installation. Careful completion of each detail will provide an auto-

matic fire and smoke detection system that will be dependable and

give reliable operation.
Connection instructions are mounted inside the chassis cover of the

CP-48. Additional wiring information is provided in this manual. Any

questions regarding the equipment or installation should be directed

to Siemens Building Technologies, Inc., or an authorized represen-

tative. Do not make any alteration without first consulting the above.

3.1 Mounting Control Units

 (Reter to Figure 2):

The Control Unit should be securely fastened to a shock and

vibration free surface in a clean, dry area. It must be mounted

greater than 3 ft., but less than 6 ft. from the floor. The location

should be easily visible and readily accessible for maintenance and

allow sufficient clearance to open the hinged front door.
Local regulations or codes generally require all wiring to, from, and

between units to be carried in 

1

/

2

"-

3

/

4

"

 

knockouts provided in the

top and bottom of the control unit. #18 AWG 300V insulation,

color coded wire is recommended for the detector circuits. A larger

size may be used if desired. For the DC power input use #14 AWG

300V wire.

3.2 Power Requirements:

The Model CP-48 Control Unit is designed to be operated from a

48 VDC power source having the positive line grounded, such as

is available in telephone community dial offices. The 48 VDC input

powers all internal circuitry. The DC voltage may vary between the

limits of 42 and 55 volts and the limits should not be exceeded. The

CP-48 Control Unit, ungrounded leg, must be connected through a

separate circuit breaker or fuse directly to the DC power supply. No

other equipment may be supplied from this separate circuit breaker

or fuse. Wire must be run continuously from power source to

terminals in Control Unit. Refer to Wiring Diagram (Figure 3) for

terminal connections.

3.3 Installation of Conduit and Outlet Boxes:

Install outlet boxes and run conduit between boxes and control unit.

Use 4"x2

1

/

8

" deep octagon boxes for ionization, photoelectric, flame,

and plug-in thermal detectors. Do not mount boxes in direct air flow

from air-conditioning or ventilating system supply registers.

The control unit, and all detectors and alarm circuit conduit, must be

properly grounded. Insure that all conduit has clean threads and

makes good electrical contact between control unit and outlet boxes.

3.4 Installation of Detector Bases:

a. Wiring 

(Refer to Figure 3):

Run wire in accordance with wiring diagram. Use at least #18 AWG

300 volt insulation, color coded wire for the detector circuits. Wiring

between control unit and first detector base, and all subsequent

detector bases must be continuous; no splices, wire nuts, solder or

any other type connection is permissible. On rare occasions an

exception may be necessary due to an extremely long run. In this

case, the splice must be soldered.

Figure 2

Mounting Data

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for CP-48

Page 1: ... and Smoke Detection and Alarm System Fire Safety Siemens BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Technical Manuals Online http www tech man com firealarmresources com ...

Page 2: ...be returned to manual position before the system will reset 2 2 If Fire Alarm Sounds a Notify the Fire Department If the system is connected to the Fire Department or a central station this is done automatically by the control equipment Keep in mind that the Fire Department or central station should be notified when resetting the system b If fire is not apparent DO NOT RESET SYSTEM Locate the dete...

Page 3: ...ted from a 48 VDC power source having the positive line grounded such as is available in telephone community dial offices The 48 VDC input powers all internal circuitry The DC voltage may vary between the limits of 42 and 55 volts and the limits should not be exceeded The CP 48 Control Unit ungrounded leg must be connected through a separate circuit breaker or fuse directly to the DC power supply ...

Page 4: ... lines to chassis and conduit There should be at least 10 meg resis tance reading between wires and conduit or ground c Connect wires to appropriate terminals of the Model CP 48 For base wiring follow instructions included with base d The manufacturer s service representative will then install detectors and check sensitivity 3 6 Test for System Operation a See that the CP 48 Control Unit is in nor...

Page 5: ... switch in off normal or silenced position during non alarm condition Note items 2 and 3 above These conditions cause a change of state of the trouble relay contacts only and not a visual trouble indication Trouble Condition Trouble contacts in trouble state 1 Check main power terminals 1 to 2 2 Check fuse F1 3 Check detector circuit voltage terminals 3 to 4 Alarm Condition alarm contacts in alarm...

Page 6: ...ESISTOR VALUES ARE IN O s OHMS 1 4W 2 UNLESS OTHERWISE SPECIFIED ALL CAPACITOR VALUES ARE IN µFD MICROFARADS 3 DIODES CR5 CR9 ARE IN4003 4 KT 2 SHOWN ENERGIZED KA 4 SHOWN DE ENERGIZED CP 48 Schematic Technical Manuals Online http www tech man com firealarmresources com ...

Page 7: ...s BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Technical Manuals Online http www tech man com firealarmresources com ...

Reviews: