background image

2

1.0 INTRODUCTION

The 

 Model CP-48 Control Panel is a single zone fire alarm

control unit, which may employ the specified ionization, thermal or

photoelectric type detector. This unit has been especially designed to

operate from a 48 volt DC power input source such as is available in

telephone community dial offices. The front cover contains a manual

fire alarm station and entry key lock. Displayed through the front cover

are the; “Power On,” “Alarm,” and “Trouble” Visual Indicators. Within

the control panel are a fire alarm “Reset/Lamp Test” switch, a switch to

silence the panel contained audible alarm, two sets of isolated alarm

relay contacts, and one set of trouble relay contacts.

2.0 USER OPERATING INSTRUCTIONS FOR CP-48

(Refer to schematic on inside back cover.)

2.1  Normal Stand-By Operation:

With panel connected to the 48 VDC Power Supply using the correct

polarity connection, and the initiating circuit terminated with the 1.8K

end of line resistor, the panel should display a normal condition with

only the visual “Power” indicator illuminated in the normal state.
An off normal position of the internal audible alarm selector switch

when the panel is not in alarm condition will result in a trouble

condition.
An alarm condition may be cleared or reset by operating the momen-

tary “Reset” switch. The associated manual fire alarm station must

be returned to manual position before the system will reset.

2.2 If Fire Alarm Sounds:

a.

Notify the Fire Department. If the system is connected to the Fire

Department or a central station, this is done automatically by the

control equipment. Keep in mind that the Fire Department or

central station should be notified when resetting the system.

b.

If fire is not apparent, DO NOT RESET SYSTEM. Locate the

detector initiating the alarm. The initiating detector will have the

base indicating lamp energized.

c.

After the fire is completely extinguished and all smoke and gases

are cleared from the area, reset the system by moving the Reset

Switch momentarily to the “Reset” position.

2.3 When Trouble Condition Develops:

a.

The trouble contacts will be in “trouble” state. Call your author-

ized Siemens Building Technologies, Inc. Representative. The

trouble should be diagnosed and corrected immediately.

2.4 Periodically Testing the System

:

 (Be sure to notify the

proper authorities prior to performing tests

)

a.

The system should be tested at regular intervals to insure

operational reliability and optimum performance. To test the

system, activate at least one detector. An lonization detector may

be activated by blowing smoke into the screened chamber or

holding a lighted match a few inches below it. Check that system

responds properly.

b.

Reset the system.

c.

This inspection should include checking the sensitivity of

every ionization detector using a sensitivity checker.

Figure 1

Model CP-48

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Summary of Contents for CP-48

Page 1: ... and Smoke Detection and Alarm System Fire Safety Siemens BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Technical Manuals Online http www tech man com firealarmresources com ...

Page 2: ...be returned to manual position before the system will reset 2 2 If Fire Alarm Sounds a Notify the Fire Department If the system is connected to the Fire Department or a central station this is done automatically by the control equipment Keep in mind that the Fire Department or central station should be notified when resetting the system b If fire is not apparent DO NOT RESET SYSTEM Locate the dete...

Page 3: ...ted from a 48 VDC power source having the positive line grounded such as is available in telephone community dial offices The 48 VDC input powers all internal circuitry The DC voltage may vary between the limits of 42 and 55 volts and the limits should not be exceeded The CP 48 Control Unit ungrounded leg must be connected through a separate circuit breaker or fuse directly to the DC power supply ...

Page 4: ... lines to chassis and conduit There should be at least 10 meg resis tance reading between wires and conduit or ground c Connect wires to appropriate terminals of the Model CP 48 For base wiring follow instructions included with base d The manufacturer s service representative will then install detectors and check sensitivity 3 6 Test for System Operation a See that the CP 48 Control Unit is in nor...

Page 5: ... switch in off normal or silenced position during non alarm condition Note items 2 and 3 above These conditions cause a change of state of the trouble relay contacts only and not a visual trouble indication Trouble Condition Trouble contacts in trouble state 1 Check main power terminals 1 to 2 2 Check fuse F1 3 Check detector circuit voltage terminals 3 to 4 Alarm Condition alarm contacts in alarm...

Page 6: ...ESISTOR VALUES ARE IN O s OHMS 1 4W 2 UNLESS OTHERWISE SPECIFIED ALL CAPACITOR VALUES ARE IN µFD MICROFARADS 3 DIODES CR5 CR9 ARE IN4003 4 KT 2 SHOWN ENERGIZED KA 4 SHOWN DE ENERGIZED CP 48 Schematic Technical Manuals Online http www tech man com firealarmresources com ...

Page 7: ...s BuildingTechnologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens BuildingTechnologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Technical Manuals Online http www tech man com firealarmresources com ...

Reviews: