9
Figure 7
Installation/Wiring Diagram for ADBI-60 Audibles
Powered by IXL System
Figure 8
Installation/Wiring Diagram for ADBI-60 Audibles
Powered by a Remote Power Supply (System IXL)
1. Set the CE-S address to 201 to
follow the System alarm relay.
2. Only detectors attached to the
ICON-1 can be used with the
ADBI-60.
3. The ADBI-60 turns on when
its associated detector goes
into alarm.
4. The UL listed power supply
with battery backup is rated
at 24 VDC. It must supply
enough current to handle at
least 10% of the ADBI-60s
connected to it.