12.2 How to configure station
1. Press “ ” to enter main menu.
The main menu is displayed.
2. Press “
↓
” to choose “4.Configure” and press “OK” key.
Configure window is displayed.
3. Press “
↓
” to choose “1.Configure” and press “OK” key.
Configure system window is displayed.
4. Press “
↓
” to choose “2.Station” and press “OK” key.
All stations are displayed. The text can be modified now.
5. Press “
↓
” to choose one desired station and press “OK” key.
Press “
↓
” / ”
↑
” to scroll down/up.
6. Press “
↓
” to choose “2.Station Property” and press “OK” key.
The property of the selected station is displayed. The text, A-Bus buad rate, login time
and walk-test time can be modified. Press “
↓
” / ”
↑
” to switch active window.
7. Press “OK” to save the modification and return to the previous window.
Note:
1. Now the modified text is saved temporarily. If the control unit is reset, the modified text
will be lost. If you want to save the modification for long time, please do the “Save
Configuration” operation(refer to Page 44).
2. A-Bus is a drop-down list. When it is active, press “F” and the drop-down list is displayed.
Press “
↓
” / ”
↑
” to select high(
40K bps)
, middle(25K bps) or low(16K bps) according to
on-site situation. Press “OK”.
3. Login time means if no operation or no events happen within login time under user level
2/3 control unit will return to user level 1 automatically. Valid range is 1-60 Minutes.
4. Walk-test time means when control unit do walk-test it can restore to normal mode
automatically after walk-test time. Valid range is 1-60 Minutes.
<Main Menu> L 3 A
1. RT Information
2. History Record
3. Operation
4. Configure
< Configure> L 3 A
1. Configure
2. Set Time and Date
3. Set LCD Contrast
4. Set Buzzer Volume
<Configure System> L 3 A
1. System Property
2. Station
<Configure Station> L 3 A
001 BC8001A Compact 01
002 BC8001A Compact 02
003 BC8001A Compact 03
<Configure Station> L 3 A
1. Lines
2. Station Property
<Station 02> L 3 A
Address 02.000.000
Type BC8001A Compact
Text
Status Normal
BC8001A 02
<Station 02> L 3 A
A-Bus
Login (min)
Walktest (min)
1
3
High