BC8001A Installation and Operating Instruction
Page 27/49
Isolate/Open Point
Function:
only when it is damaged or defective until it is replaced. An isolated point can not
generate any messages. As soon as replacement is finished, the isolated point must be
immediately restored to normal status again.
Status:
LCD will display isolation event automatically as “Isolation Screen”.
The isolate LED is on.
The buzzer sounds.
How to isolate/open point:
1~5 steps are the same as loop isolation/open.
6. Press “
↓
” to choose “1.Point” and press “OK” key.
All points connected with the chosen line are displayed.
7. Press “
↓
” to choose one desired point and press “OK” key.
8. Press “
↓
” to choose “1.Isolate” / ”2.Open” and press “OK” key.
Isolation status is shown/disappeared.
Isolation Screen
<Operate Points> L3 A
001 BDS051(A) 001
002 BDS031(A) 002
003 BDS121(A) 003
004 BDS132(A) 004
<Operate Lines > L3 A
1. Points
2. Isolate
3. Open
4. Test
<RT – Isoaltion:1> L1 A
- 1 Room 102 heat detector
<Operate Points > L3 A
1. Isolate
2. Open
3. Test
4. Walk-Test