because of the mechanisms of AS-Interface: The cycle time extends in this case
only by 150 µs. Only fundamental considerations e.g. the change of a slave or the
potential instability of the net recommend the correction in this case.
In practice quite a few nets in a comparable condition might work trouble-free wit-
hout ever being noticed by the user. It would be more critical if a slave would ex-
hibit a
single failure
of the class 6.
Fig 16:
Example of a net strongly disturbed. The effect of this disturbance becomes visible
only by an error analysis: The representation as a consecutive error shows that the
disturbance can be tolerated temporarily (see text).