2. Additionally
each
of the red marked ranges must be activated as described in
number 1 (that corresponds to a logical AND-conjunction within the red ranges).
3. The "
Number of Trigger Conditions
" indicates, how often the adjusted trigger
condition must be fulfilled before it is changed over to the next trigger level. If
this number is specified as "0" the trigger level is not active. This is indicated by
a red flag on the tab.
4. "
Error
" means a identification of an incorrect AS-Interface telegram. The ana-
lyser examines (just as the receivers inside master and slave) each single tele-
gram according to a set to criteria for formal correctness. These are the well-
known error protection mechanisms of AS-Interface. If the analyser finds a in-
correct telegram, this leads to triggering the trace, provided that "Error" is
marked. This function is independent of the red marked fields (so it corresponds
to a logical OR-conjunction with the red marked fields).
•
Input assistance
: Generating of the trigger conditions is simplified by the fol-
lowing:
• With the call of the trigger mask (after restart of the software or with the transi-
tion to the online statistics) the automatic assumption of the recognized slaves
into the masks is offered if the net and the analyser are active.
• Three frequently used basic adjustments are offered in the field "Template": "All
Single Slaves", "All A/B-Slaves" and "Errors". In the first two settings all mean-
ingful defaults for all slaves are entered. In the third case all possible errors in
data exchange, i.e. incorrect telegrams or missing slave responses. These ba-
sic adjustments can be manually adapted to the respective situation.
• In the upper range of the sheet several buttons are contained, with which whole
fields can be reset or set. They change between "Clear All" and "Set All" and are
coupled in a way that unreasonable combinations are avoided.
• The field "Master Data" describes the trigger conditions for the data bits D0 to
D3. These can have different meanings for each type of telegram. With some
telegram types they have fixed values and so they are redundant to the field
"Master Requests" located next to the filed "Master Data". As long as special sit-
uations do not have to be examined the button "Set All" works very well. The
selection of the trigger takes place via the AND-conjunction with the type of tele-
gram. If here special defaults are to be made, the meaning of the bit D3 for A/B-
slaves is to be considered.
• The button "OK" is created in such a way that it can be only operated if theoret-
ical meaningful settings are to be confirmed.
• If the software is loaded for the first time the manual trigger is switched off as
default setting.
• You can get the current list of the slaves over the button "Get Slave List" if you
have already made a statistics measurement.