If a trace is loaded into the PC this function can be called in the menu under "
Mea-
sure / Safety Monitor
" (fig. 15). The mask shows at first the code sequence of the
slaves in a hexadecimal form, and all status changes of safety-related slaves af-
terwards (profile S 0.B.x and S 7.B.x). The column "Pos." shows a relation to the
complete trace.
Fig 15:
Evaluation of a trace like in a safety monitor. it shows first the code sequence (in he-
xadecimal) of the two safety slaves with the addresses 1 and 2 and then the changes
between "free" and "released" for both slaves within the trace.
In this mask you can see:
• the individual code sequence of the safety slaves,
• the time of disconnections which can then be analyzed more exactly in the trace
then,
• telegram errors which did not lead to disconnection because of well timed rep-
etitions,
• code errors which can be valid telegrams and therefore, cannot not be recog-
nized elsewhere.
While switching depending on the type of slave transient conditions
arise which are represented in the evaluation. Generally transient
conditions are no errors.
The evaluation of the PC takes place in the PC. It recognizes the
safety slaves by their ID code and the code sequence from the cor-
rect data calls. The recording filter must not fade out (before switch
off) both neither the ID codes nor the data calls to the decisive safety
slaves.